Tripp-Lite SmartOnline S3MX Manual Del Propietário página 68

Sistemas ups trifásicos
Ocultar thumbs Ver también para SmartOnline S3MX:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 71
10. Specifications
Model
EXTERNAL BATTERIES (S3M100KX, S3M120KX, S3M160KX and S3M200KX require external batteries to operate.)
Float Voltage
Boost Charging
End of Discharge
Charger Temperature Compensation
PHYSICAL
Dimensions (H x W x D)
Unit Weight (With Internal Batteries)
Unit Weight (Without Internal Batteries)
ENVIRONMENT
Operating Temperature
Storage Temperature
Operating Humidity
Operating Altitude
Audible Noise
Heat Dissipation (100% Load)
Heat Dissipation (50% Load)
MANAGEMENT
Network Management Interface
Control Panel
Contact Closure Interface
Remote Emergency Power Off (REPO)
RS-232
STANDARDS
Safety
EMC/EMI
Ingress Protection Rating
CE Marking
RoHS Compliant
Quality Management System
OTHER INFORMATION
Colour
Mobility
ACCESSORIES (Sold Separately)
Scalable Battery Cabinets
Network Management Card
Remote Environmental Sensors
(Require WEBCARDLX.)
Contact Closure Card
External Bypass Panel
Scalable Charger Board Kits
Parallel Cable Kit
Battery Temperature Compensation
Thermostat Kit
*If the UPS is installed or used in a place where the altitude is above than 1000 m, the output power must be de-rated 1% per 100 m.
Note: Product specifications are subject to change without notice.
S3M100KX
S3M120KX
-3 mV/Cell/°C (Requires optional TEMPC100200 thermostat kit.)
1015 x 567 x 945 mm
N/A
197 kg
0 to 40˚ C (< 25˚ C for optimal battery lifespan.)
0 to 35˚ C (UPS with Batteries), -15 to 60˚ C (UPS without Batteries)
< 1000 m (Derate output power by 1% per 100 m above 1000 m.)
< 70 dBA at 1 m
19600 BTU/hr
23507 BTU/hr
9974 BTU/hr
11048 BTU/hr
Requires optional WEBCARDLX. (Monitor, control and reboot the UPS using embedded
HTML5 web, SSH/telnet and SNMP interfaces. Supports centralised management through
integration with a wide range of Network Management Systems and DCIM platforms.)
Large 254 mm / 10 in. colour LCD touchscreen with supplemental LEDs. (Monitor, control,
configure and diagnose the UPS from the display.)
Requires Optional RELAYCARDSV Programmable Relay I/O Card
Feature Included (Default: Normally Closed)
IEC 62040-1:2008+A1:2013 (TUV Approval)
EN 62040-2:2006 (Category C3) (TUV Approval)
Support 5 min. to 3 h runtime at 100% load. Available models include BP480V100-NIB,
BP480V100, BP480V65-NIB, BP480V65, BP480V40-NIB, BP480V40.
WEBCARDLX (Monitor, control and reboot the UPS using embedded HTML5 web platform,
SSH/telnet or SNMP . Supports centralized management via third-party NMS or DCIM
E2MT (Temperature Sensor); E2MTDO (Temperature Sensor with Digital Outputs);
E2MTDI (Temperature Sensor with Digital Inputs);
E2MTHDI (Temperature/Humidity Sensor with Digital Inputs)
Contact your local sales representative or distributor for more information.
CBKIT30-40
CBKIT30-80
(Adds 4A; Max 2)
(Adds 8A; Max 2)
68
S3M160KX
13,65V/Battery; 2,27V/Cell
14,1V/Battery; 2,35V/Cell
10V/Battery; 1,67V/Cell
1455 x 567 x 995 mm
N/A
N/A
232 kg
309 kg
0 to 95% (Non-Condensing)
31343 BTU/hr
14731 BTU/hr
Included (Service Only)
IP20
Yes
Yes
ISO 9001
RAL 9005 Jet Black
Casters
(NIB=No internal batteries.)
platform.)
RELAYCARDSV
P100200KIT
TEMPC100200
S3M200KX
N/A
343 kg
< 73 dBA at 1 m
39179 BTU/hr
18414 BTU/hr
N/A

Publicidad

Tabla de contenido

Solución de problemas

loading

Este manual también es adecuado para:

S3m100kx, s3m120kx, s3m160kx, s3m200kx

Tabla de contenido