Connection Diagram Wrga-02; Connection In A Generator With Auxiliary Coil And Three-Phase Sensing Voltage - WEG WRGA-02 Manual De Instalación, Operación Y Mantenimiento

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

www.weg.net
15.

CONNECTION DIAGRAM WRGA-02

15.1 CONNECTION IN A GENERATOR WITH AUXILIARY COIL AND THREE-PHASE
SENSING VOLTAGE
Auxiliary
F +
Exciter field
Exciter Field
Configuration for 160V to 300V
jumper on pins 1-2
JR
JS
JT
JCR
¹ Item not supplied by WEG;
² 5A/250Vac switch to turn ON/OFF the regulator;
³ JR, JS and JT jumpers – Sensing voltage selector (pins 1-2 = 160 to 300Vac, pins 2-3 = 320 to 600Vac);
4
JCR jumper - Sensing voltage type selector (pins 1-2 = three-phase sensing voltage, pins 2-3 = single-phase sensing voltage).
ATTENTION
1. Before connecting the regulator to the generator, verify in the installation manual, the rated sensing
voltage;
2. The sensing voltage can be different than the generator phase voltage. Note the point where the
sensing voltage is taken from (middle of the phase or complete phase).
3. If the sensing voltage is not equal to the output voltage of the generator, do not make the
connections without consulting the service department.
20
l
Automatic Voltage Regulator – GRT7-TH4-R2
Generator
Switch On/Off
2
Auxiliary
Coil
coil
3
E3/4
F+
Terminals inside
conected
F-
F -
WRGA-02
3
Configuration for three-phase sensing
voltage jumper on pins 1-2
Figure 15.1 - Sensing voltage 160 to 300Vac and 320 to 600Vac.
N
R
S
T
Potentiometer for voltage external
4
.
N
R
S
T
1
adjustment
(5K/3W)
Configuration for 320V to 600V
jumper on pins 2-3
JR
JCR
3
JS
JT

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Wrga-02/d

Tabla de contenido