15.3 CONNECTIONS IN A GENERATOR WITH AUXILIARY COIL AND SINGLE-PHASE
SENSING VOLTAGE
F +
Exciter field
Configuration for 160V to 300V
jumper on pins 1-2
JR
JS
JT
JCR
1
Item not supplied by WEG;
2
5A/250Vac switch to turn ON/OFF the regulator;
3
JR, JS and JT jumpers – Sensing voltage selector (pins 1-2 = 160 to 300Vac, pins 2-3 = 320 to 600Vac);
4
JCR jumper - Sensing voltage type selector (pins 1-2 three-phase sensing voltage, pins 2-3 single-phase sensing voltage).
ATTENTION
1. Before connecting the regulator to the generator, verify in the installation manual, the rated sensing
voltage;
2. The sensing voltage can be different than the generator phase voltage. Note the point where the
sensing voltage is taken from (middle of the phase or complete phase).
3. If the sensing voltage is not equal to the output voltage of the generator, do not make the
connections without consulting the service department.
22
l
Automatic Voltage Regulator – GRT7-TH4-R2
Generator
Switch On/Off
2
Auxiliary
coil
3
F+
Terminals inside
conected
F-
F -
WRGA-02
3
Configuration for single-phase sensing
voltage jumper on pins 2-3
Figure 15.3 - Sensing voltage 160 to 300Vac and 320 to 600Vac
E3/4
N
R
4
.
N
R
S
T
Potentiometer for voltage external
adjustment
1
(5K/3W)
Configuration for 320V to 600V
jumper on pins 2-3
JR
3
JS
JT
JCR