Technical Data - gefran 2300 Manual De Uso

Visualizador / interceptador veloz
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 66
108
96
48
44,5
152
10
!
For correct installation, follow the instructions
contained in this manual
I
NPUTS
Precision 0.2% f.s. ±1 digit
Sampling time 2msec
Strain-gauge
350Ω (for pressure, force, etc), sensitivity 1.5/2/2.5/3/3.3mV/V, positive
polarization, symmetrical and negative.
Potentiometer
≥ 350Ω, Ri > 10 MΩ
DC - Linear
0...50mV / -25...25mV / -50...0mV / 0...60mV / -30...30mV / -60...0mV
0...100mV / -50...50mV / -100...0mV / 0...1V / -500...500mV / -1V...0V
0...10V / -5...5V / -10V...0V
For all inputs in voltage
Ri ≥ 1 MΩ / 0...20mA / 4...20mA, Ri = 50Ω
32-section custom linearization available.
Auxiliary inputs
Two remote analog trip setpoints, absolute or relative to local set.
0...10V, Ri ≥ 1MΩ / 0...20mA, Ri = 50Ω / 4...20mA, Ri = 50Ω
Digital
Optically isolated1500V.
2 inputs with configurable function: tare zero, reset trip memory, reset
peak memory, check calibration, enable remote setpoints, Hold
function.
- NPN or PNP 24V/4mA
O
UTPUTS
Relay
With 5A/250Vac contacts at cosϕ = 1 (3.5A at cosϕ = 0,4).
Spark suppression on NO contacts.
Logic
In voltage for static relay control (SSR)
23Vdc, Rout = 470Ω (20mA, max. 12V).
Retransmission
1500V isolation.
Retransmission output for input, peak values, remote sets, alarm
setpoint, configurable scale settable from panel keys
0...10Vdc, -5...5Vdc, -10...10Vdc, Rload > 500Ω
0...20mA, 4...20mA Rmax = 500Ω
Resolution 4000 points.
Response time 8 msec.
2300
FAST INDICATOR / ALARM UNIT
1 • INSTALLATION
• Dimensions and cut-out
Panel mounting.
Front panel dimensions: 96x48mm./3.78"x1.89" (1/8DIN); depth:152mm /5.98"
Cut-out dimensions: 92 (+0.8/-0)x45 (+0.6/0)mm/3.62" (+0.03/-0)x1.77" (+0.02/-0)".
To lock the instrument, insert the two blocks into the dovetail guides (split), diagonally
115
(vertically) to one another and tighten with the screws. To install two or more
instruments side by side or stacked, use the locking blocks and the following hole
measurements:
side by side - Base (96 x n)-4 / (3.78 x n)-0.15" Height 45 (+0.6/-0) / 1.77" (+0.02/-0)
70
column - Base 92 (+0.8/-0) / 3.62" (+0.03/-0) Height (48 x n)-3 / (1.89" x n)-0.11"
where "n" is the number of instruments.
92
CE MARKING: EMC (electromagnetic compatibility) conformity to EEC Directive 89/336
with reference to generic standards EN61000-6-2 (immunity in industrial environment)
and EN50081-1 (emission in residential environment).
BT (low voltage) conformity to EEC Directive 73/23 modified by Directive 93/68.
MAINTENANCE: Repairs may be done only by trained and specialized personnel. Cut
power to the instrument before accessing internal parts. Do not clean the case with
hydrocarbon-based solvents (trichloroethylene, gasoline, etc.). The use of such solvents
will compromise the instrument's mechanical reliability. Use a clean cloth moistened
with ethyl alcohol or water to clean external plastic parts.
TECHNICAL SERVICE: GEFRAN has a technical service department. Defects deriving
from any use not conforming to this manual are excluded from the warranty.
2 • TECHNICAL DATA
S
L
ERIAL
INE
Optically isolated 4 wires. The instrument is available with Current Loop
(1200 baud) or RS485 (1200/2400/4800/9600 baud) interface.
Protocol: GEFRAN CENCAL or MODBUS
S
S
/ T
ENSOR
UPPLY
RANSMITTER
1500V isolation
5, 10 or 15Vdc/200mA or 24Vdc/100mA
P
S
OWER
UPPLY
100...240Vac/dc ±10% / 11...27Vac/dc ±10% 50...60Hz; 12VA max
Protected by internal fuse not serviceable by user.
A
C
MBIENT
ONDITIONS
Working temperature: 0...50°C
Storage temperature: -20...70°C
Humidity: 20...85%Ur non-condensing
A
LARMS
3 (10) alarm setpoints settable in absolute value with functions
completely configurable from panel keys
(Direct / Reverse / Relative / Symmetrical relative)
- Setting of setpoint along entire selected scale.
- Trip hysteresis settable from panel keys.
- Function: minimum or maximum trip points with saving of trip (LATCH)
selectable during configuration.
Relays energized or de-energized in trip status: selected from panel
keys.
Trip can be excluded during power-up phase until input variable
exceeds set trip point.
Relay trips when variable drops below trip point. Output activation can
be timed.
Trip response time:
for Out1 ... Out 2 = 2msec
for Out 3 ... Out 10 = 8msec
G
MD8
EFRAN
EXPANSION
replacing output 3
- with 8 additional alarm setpoints .
W
EIGHT
450g
18

Hide quick links:

Publicidad

Tabla de contenido
loading

Tabla de contenido