Configuration 3 (CFG.3).
Use the F key to confirm set values and go to setting of next parameter.
In.tYP
type of input e polarization:
In.tYP
0
1
Strain gauge (Pressure, force, etc)
2
4
5
Linear (V, I, Pot)
6
+8
Custom linearization (*)
+16
Inputs algebraic sum function (main input +
remote input 1)
+32
"Remote AD converter" function: acquisition of
process variable directly from serial line (CENCAL
only) (in range 0-16000 points) instead of from
instrument's analog input.
+64
To cancel messages _Lo_ (off scale low) and _Hi_
(off scale high) from display excluding custom
linearization.
(*) In this case, set the custom linearization table to 32 segments (see CFG.4)
In.Cod sensitivity identification code at input.
STRAIN GAUGE
In.Cod
Sensitivity (mV/V)
0
1.5
1
2
2
2.5
3
2
4
3.3
5
1.5
6
2
7
2.5
8
3
9
3.3
10
1.5
11
2
12
2.5
13
3
14
3.3
15*
Trasmitter 0...10V
16*
Trasmitter 0...20mA
17*
Trasmitter 4...20mA
(*) positive polarization only (In.tYP = 0). See also "Details on linear scales."
FiLt
constant programming of digital filter time, settable in range 0-2.00 sec. It is advisable to turn on the filter at the limit of
the admitted trip time. Set = 0 to turn off filter.
Fild
constant programming of digital filter time on display. Value settable in range 0...9.9 sec. Set -0 to turn off filter. Does
not affect trip time .
dEC.P
position of decimal point or number of decimal digits in range 0/1/2/3/ +4 to display value multiplied by 10..
oFSEt
offset of input in range -999/999 in scale units.
Lo.Lin Minimum linear scale value for input in range -9999/+9999. (*).
Hi.Lin
Maximum linear scale value for input in range -9999/+9999. (*).
(*) If dEcP = n + 4 (display value multiplied by 10), the minimum limit becomes -1999 (displayed: -19990)
8 • CONFIGURATIONS
Probe type
Energizing (V)
In.Cod
5
10
15
Signal polarization
Positive (ex: 0...10mV)
Symmetrical (ex: -10...10mV)
Negative (ex: -10...0mV)
Positive (ex: 0...10V)
Symmetrical (ex: -5...5V)
Negative (ex: -10...0V)
LINEAR
Signal
0
0-50mV
1
0-60mV
2
0-100mV
3
0-1V
4
0-10V
5
0-20mA
6
4-20mA
Pot. ≥350Ω
7
Power 10V
Control
"Probe input"
configuration
as well
27