Note:
Make sure that the detector's physical ID number is identical to the ID number you select during programming.
3. Place the cursor on the TYPE field and use the
WatchIN DT detector.
4. Press
/
5. Repeat the process for the other BUS detectors.
2. Assigning the WatchIN DT to a Zone
1. From the main installer menu enter Zones: One by One option (Quick key [2][1])
2. Select the zone number that you want to assign the BUS detector.
Note:
If you have defined a BUS Zone Expander, select a zone number from the virtual zones (defined by the BUS
zone expander).
3. Define Partitions, Groups, Zone Type and Zone Sound.
4. In the Termination category select [5] BUS Zone followed by
The following display appears:
Z:001
LINK TO:
ID:01
TYPE=IDT25
5. Select the BUS zone number to assign to the programmed zone. The type field will be
updated automatically when selecting the zone.
6. Press
/
the following display appears:
Z:001
Z:001
RESPONSE:
RESPONSE:
N/A-BUS ZONE
N/A-BUS ZONE
7. Press
/
Configuring the WatchIN DT Parameters
1. To access the WatchIN settings option press [2][0][3] from the main installer menu. The
following display appears:
B- ZONE PRMS:
-
ZONE#=001
2. Select the zone that the BUS zone was assigned to and press
now program the WatchIN parameters as follows:
Zones Miscellaneous: BUS Zone
Quick Keys
Parameter
[2][0][3][zzz]
LEDS
[1]
Defines the LEDS operation mode
[2][0][3][zzz]
Off
[1][1]
Disables the LEDS operation
[2][0][3][zzz]
Red Only
[1][2]
Only the Red led will operate. This option is highly recommended to avoid the
possibility that the intruder will "Learn" the detector behavior.
[2][0][3][zzz]
3 LEDS
[1][3]
All 3 LEDs will operate.
[2][0][3][zzz]
Detection Sensitivity
[2]
Defines the sensitivity of the detector(MW + PIR)
to confirm.
. The loop response category is not applicable to a BUS zone and
, assign label and press
(0:01)
WatchIN Installation Manual
/
key to select IDT25 for the
/
/
.
/
Default
3 LEDS
Normal
.
. You can
19