System Parameters
System: System Control
Quick Keys
Parameter
[1][2][36]
AM=Tamper
(UK Version)
Used to determine the operation of Anti Masking detection
Yes: Anti mask violation will activate tamper alarm.
No: Anti mask violation will be regarded as trouble event.
[1][2][37]
VBR=Tamper
Used to determine the operation of the vibration detection (applicable to
versions with Vibration sensor installed)
Yes: Vibration detection will activate tamper alarm.
No: Vibration detection will be regarded as trouble event.
Diagnostics
The ProSYS enables you to test parameters that reflect the operation of the detector.
1. From the main user menu press
2. Enter the Installer code (or sub-installer) and press
3. Press [9] [1] to for the BUS Zones diagnostic menu.
4. Enter the digit of the zone that you want to test and then press
will perform the diagnostics test and a list of test parameters will appear, as indicated in the
table below.
5. Use the keys
User Menu: 4) Maintenance
Quick Keys
Parameter
[4][9][1][zzz]
Detector Input Voltage: Display the input voltage of the detector.
PIR 1 Level: PIR channel 1 DC level. Range 0.1v - 4v
PIR 1 Noise Level: PIR channel 1 AC level. Range 0VAC (No noise) - 4VA
PIR 2 Level: PIR channel 2 DC level. Range 0.1v - 4v
PIR 2 Noise Level: PIR channel 2 AC level. Range 0VAC (No noise) - 4VA
MW 1 Level
MW 1 Noise Level
MW 2 Level: MW channel 2 DC level Range 0.1v - 4v
MW 2 Noise Level: MW channel 2 AC level (0VAC (No noise) - 4VAC
[4] to access the Maintenance menu.
/
/
9) Diagnostic
MW channel 1 DC level Range 0.1v - 4v
:
MW channel 1 AC level (0VAC (No noise) - 4VAC)
:
WatchIN Installation Manual
Default: No
No
/
to view the diagnostics test results.
1) BUS Zone
.
/
. The system