GB

TECHNICAL CHARACTERISTICS

Auxiliary supply
Rated voltage Ue
Operating limit
Rated frequency
Maximum consumption
Maximum dissipation
Maximum power dissipated by output contacts
Immunity time for microbreakings
No-voltage release
Current input
Rated current Ie
Operating limit
Constant overload
Type of measurement
Short time withstand current
Dynamic limit
Power consumption
UL Rating
Control range
Power factor setting
Reconnection time of the same step
Sensitivity
Output relay
Number of outputs❶
Type of output
Maximum current at contact common
Rated current Ith
Rated capacity of NO contacts
Rated capacity of NC contact
Electrical life at 0.33A, 250VAC and AC11 load conditions
Electrical life at 2A, 250VAC and AC11 load conditions
Electrical life at 2A, 400VAC and AC11 load conditions
UL Rating
Operating ambient conditions
Operating temperature
Storage temperature
Relative humidity
Overvoltage category
Maximum pollution degree
Connections
Type of terminal
Cable cross section (min - max)
Tightening torque
UL Rating
Cable cross section (min - max)
Enclosure
Version
Material
Degree of protection
Weight
Reference standards
IEC/EN 61010-1; IEC/EN 61000-6-2; ENV 50204; CISPR 11/EN 55011; 61000-3-3; IEC/EN 60068-2-61; IEC/EN60068-2-27; IEC/EN60068-2-6; UL508; CSA C22.2 No.14-95.
Certifications
cULus
UL "Marking"
- Use 60°C/75°C copper (CU) conductor and wire size range 18-12 AWG, stranded or solid.
- For use on a flat surface of a Type 1 Enclosure.
1 output contact is galvanically isolated.
Pollution degree 2 when outputs used with 400VAC load.
DCRK5
DCRK7
380...415VAC (other values on request)
-15%...+10% Ue
50 or 60Hz ±1% (self configurable)
6.2VA
2.7W
0.5W with 5A
≤30ms
≥8ms
5A (1A on request)
0.125...6A
0.05...6A (P12 programmed as
dir
+20%
True RMS
10Ie for 1s
20Ie for 10ms
0.65W
Supplied by an external current transformer (low voltage). Max 5A
0.80ind...0.80cap
5...240s
5...600s/step
DCRK5
DCRK7
5
7
4 + 1 NO
6 + 1 NO
12A
5A
1.5A 250VAC (AC15) - 1.5A 400VAC (AC15)
1.5A 250VAC (AC15) - 0.75A 400VAC (AC15)
6
5x10
ops
5
4x10
ops
5
2x10
ops
B300
-20°...+60°C
-30...+80°C
<90%
3
3❷
Removable / Plug-in
2
0.2 - 2.5 mm
(24 - 12 AWG)
0,5 Nm (4.5LBin)
2
0.75 - 2.5mm
(18 - 12 AWG)
Flush mount
Thermoplastic NORYL SE1 GNF2
IP54
440g
460g
DCRK8
DCRK12
5VA
3W
Direct or
rEu
Inverse)
DCRK8
DCRK12
8
12
7 NO + 1 C/O
11 NO + 1 C/O
Thermoplastic LEXAN 3412R
IP41 (IP54 with protection cover)
740g
770g
15