GB
TECHNICAL CHARACTERISTICS
Auxiliary supply
Voltage input
Current input
Programmable input set as temperature sensor input
Programmable input set as digital input
Control range
Serial communication lines
Clock/calendar (RTC) function
Output relay
Operating ambient conditions
Connections
Enclosure
Compliance
Certifications
UL "Marking"
❶
1 output contact is galvanically isolated.
❷
Pollution degree 2 when outputs used with 400VAC load.
20
Rated voltage Ue
Operating limit
Rated frequency
Maximum consumption at rated voltage
Maximum dissipation at rated voltage
Maximum power dissipated by each output contact
Immunity time for microbreakings
No-voltage release
Type of input
Measuring rated voltage
Measuring range
VT Ratio setting
Measuring method
UL Rating - Measuring rated voltage
Rated current Ie
Operating limit
Constant overload
Type of measurement
Short time withstand current
Dynamic limit
Input power
UL Rating
Measuring range
Type of sensor
Maximum connection length
Input voltage
Input current
Input impedanc
Input delay
Maximum connection length
Power factor setting
Reconnection time of the same step
Sensitivity
RS485 serial interface
RS232 serial interface
Battery type
Battery duration
Number of outputs
Type of output
Maximum current at contact common
Rated capacity Ith
Rated capacity of NO contacts
Rated capacity of NC contact
Electrical life at 0.33A, 250VAC and AC11 load conditions
Electrical life at 2A, 250VAC and AC11 load conditions
Electrical life at 2A, 400VAC and AC11 load conditions
UL Rating
Operating temperature
Storage temperature
Relative humidity
Overvoltage category
Maximum pollution degree
Type of terminal
Cable cross section (min-max)
Tightening torque
RS232 interface
UL Rating - Cable cross section (min - max)
Version
Degree of protection
Weight
DCRJ8
Dual voltage 110...127VAC and 220...240VAC
-15% ... +10% Ue
50 or 60Hz ±5%
9.7VA
5W
0.5W with 5A - 250VAC
≤45ms
≥8ms
L1-L2-L3 or L1-N
100...690VAC
85...760VAC 50/60Hz ±5%
1...250
True RMS
100...600VAC
5A (1A on request)
0.125 ... 6A
0.05...6A (P12 programmed as
Direct or
dir
+20%
True RMS
10Ie for 1second
20Ie for 10ms
0.3VA
Supplied by an external current transformer (low voltage).
Max 5A
-40 ...+85°C
NTC
3m
4,5VDC
≤4,5mA
10kΩ
≥150ms
3m
0.80ind ... 0.80cap
5 ... 240 seconds
5 ... 600 sec/step
Isolated, with programmable baud-rate 1200..38400 bps
Programmable baud-rate 1200..38400 bps
CR2032 - 3V lithium not rechargeable
> 10 years
8
7 NO + 1 C/O
11 NO + 1 C/O
12A
250VAC 5A
1.5A 250VAC (AC15) - 1.5A 400VAC (AC15)
1.5A 250VAC (AC15) - 0.75A 400VAC (AC15)
6
5x10
5
4x10
5
2x10
B300
-20 ... +60°C
-30 ... +80°C
<90%
3
3❷
Removable / Plug-in
2
0.2 - 2.5 mm
(24 - 12 AWG)
0.5 Nm (4.5 lbin)
RJ6/6 connector
2
0.75-2.5mm
(18 - 12 AWG)
Flush mount
IP41 (IP54 with protection cover) - IP20 terminals
940g
IEC/EN 61010-1, IEC/EN 61000-6-2, IEC/EN 61000-6-3,
ENV 50204, IEC/EN 61000-3-3,
IEC/EN 60068-2-61, IEC/EN60068-2-27, IEC/EN60068-2-6,
UL508, CSA C22.2 No.14
GOST, cULus
- Use 60°/75°C copper (Cu) conductor and wire
size range 18-12 AWG, stranded or solid.
- For use on a flat surface of a Type 1 Enclosure.
DCRJ12
9.7VA
5.5W
Inverse)
rEu
12
980g