Connection Data - Lenze E94AYAB Instrucciones Para El Montaje

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

Connection data

X80
SSP9400X80
Terminal data
Rigid
Wire end ferrule,
insulated
Twin wire end
ferrule
Stripping length / contact length: 10 mm
Information for the exchange of modules of different hardware versions
up to HW: VB
SI1
GI
SI2
GO
24O
DO1
EDK94AYAB DE/EN/FR/ES/IT 5.1
Marking
Description
SIA
Input first shutdown path
GI
GND potential for SIA/SIB
SIB
Input second shutdown path
GO
GND potential feedback
24O
24 V supply feedback
DO1
Non−safe signalling output: "Safe
pulse inhibit"
Conductor cross−section
2
[mm
]
0.2 ... 2.5
0.2 ... 1.5
0.5 ... 1.0
Electrical installation
[AWG]
24 ... 12
24 ... 16
20 ... 18
from HW: VC
SIA
GI
SIB
GO
24O
DO1
l
Connection data
Electrical data
SIA: I
= 160 mA
typ
LOW: −3 ... 5 V,
HIGH: 15 ... 30 V,
SIB: I
= 28 mA
typ
Supply through safely
separated power
supply unit
(SELV/PELV)
24 V, max. 0.7 A,
short−circuit−proof,
LOW−active,
Supply through safely
separated power
supply unit
(SELV/PELV)
Tightening torque
[Nm]
[lb−in]
Spring terminal
Comment
The exchange of the spring
terminal is required!
4
27

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Sm100

Tabla de contenido