Panel Mounting

I
The enclosure must be in accordance with all local and national electrical
codes.
I
Lutron does not recommend using a door to enclose the front of a panel, since
this restricts airflow to the GRAFIK Eye Control Units and Interfaces.
I
If mounting multiple Control Units or Interfaces in an enclosure:
1. Ambient temperature within an enclosure must remain between
32°—104° F (0°—40° C).
2. If not mounting in a metal enclosure, all units must be mounted in a
wallbox.
I
To improve heat dissipation of Power Interfaces, remove the faceplate from the
unit.
GRAFIK Eye Control Units and Interface Units dissipate heat when
operating. Obstructing these units can cause malfunction to both the
Control Unit and the Interface if ambient temperature does not remain
between 32°—104° F (0°—40° C).

Troubleshooting Guide

Symptom
Lights do not come on.
Lights turn on/off
unexpectedly.
2:22 PM
Page 7
Causes
Power is off
Miswire
Bulb(s)/lamp(s) burned out
GRAFIK Eye 3000 Control
Unit
Interface is overloaded
Load Type
GRAFIK Eye 3000 Control
Unit
PB
4 1/2 in. (11 cm) MINIMUM
4 1/2 in. (11 cm) MINIMUM
FDBI
Solution
Restore power to the PB/ELVI/FDBI.
Restore power to the Control Unit.
Confirm wiring per wiring diagrams.
Replace bulb(s)/lamp(s).
Refer to troubleshooting section of GRAFIK Eye Control Unit Installer's
Guide.
Check for excess load, proper mounting, and adequate air convection.
Allow unit to cool.
Confirm that the load type being switched/dimmed is compatible with
the PB/ELVI/FDBI.
Refer to the troubleshooting section of GRAFIK Eye Control Unit
Installation Guide.
7