GRAFIK Systems
Installation Instructions
Occupant Copy
Features
GRX-IO
• Integrates a GRAFIK Eye lighting control system with
equipment that has contact-closure I/O, including:
- Motion and occupant sensors.
- Timeclocks and push buttons.
- Motorized projection screens, skylights, window shades,
and movable walls.
- AV equipment.
- Security systems.
• May be programmed to control any combination of one to
eight GRAFIK Eye 3000 or 4000 Series control units.
Inputs/Outputs:
• Provides five inputs and five outputs.
• Provides both normally open (NO) and normally closed
(NC) contacts.
• Using the inputs, contact closures in other equipment can
operate control units to:
- Select scenes.
- Run sequences (loop through scenes).
- Lock control units.
- Activate panic mode (lights go full on).
- Adjust scenes to reflect status of movable walls.
- Turn lights on or off based on room occupancy.
• Using the outputs, scene changes in control units can:
- Trigger outputs to control other equipment.
- Provide status feedback to other equipment.
Four Types of Configuration:
1.4S Scene Selection Control: Provides for remote control
of GRAFIK Eye 3000 or 4000 Series control units. Can be
used to select any group of four scenes and turn the
system and all corresponding lighting off.
Maintain Outputs: Allows the selection of up to 5 contact
closures to other manufacturers' A/V equipment.
Momentary Outputs: Allows the selection of projection
screens requiring momentary output closures.
2.4Q Special Function Control
Sequencing: Cycles the preset light levels from scene 1
through scene 4 (or 5 through 16) and back to scene 1 (or
5) looping indefinitely and using the programmed fade
times for each scene.
Zone Lockout: Prevents modifications to set light levels
on the GRAFIK Eye control unit. Only temporary changes
can be made.
Scene Lockout: Prevents changing of the selected scene
or preset levels on all GRAFIK Eye control unit(s) and
wallstations.
Panic: Activates scene 16 on assigned GRAFIK Eye
control unit(s) and places them in Scene Lockout. Toggle
of this closure will return controls to their status before
Panic was activated.
R
Please Read
GRX-IO and OMX-IO
Control Interfaces
PELV (Class 2: USA) Devices 12 - 24 V
3.4PS Partition Control: Allows independent (partition
closed) or parallel (partition open) operation of multiple
GRAFIK Eye control units.
4.OS Special Control
OS1 Occupant Sensor Scene 1/Off: maintained
contact so occupancy sensor can turn ON assigned
GRAFIK Eye control unit(s) while still allowing scene
changes once room is entered.
Note: Use 4S function if occupant sensor provides a
momentary closure.
OS2 Occupant Sensor Off Only: Occupant must turn
lights on manually, while still allowing energy-saving
benefits.
OMX-IO
• Integrates GRAFIK 5000/6000/7000, LCP128, and
Softswitch128 systems with equipment that has contact-
closure I/O, including:
- Motion and occupant sensors.
- Timeclocks and push buttons.
- Motorized projection screens, skylights, window
shades, and movable walls.
- AV equipment.
- Security systems.
• Use the GRAFIK Systems processor panel to set up the
OMX-IO interface for different modes, functions, and
momentary/maintained inputs and outputs.
Inputs/Outputs:
• Provides five inputs and five outputs.
• Provides both normally open (NO) and normally closed
(NC) contacts.
• Using the inputs, contact closures in other equipment
can operate controls to:
- Select scenes.
- Turn lights on or off based on room occupancy.
• Using the outputs, scene changes in control units can:
- Trigger outputs to control other equipment.
- Provide status feedback to other equipment.
200 mA