4
Technical data
General data and operating conditions
4
Technical data
General data and operating conditions
Conformity and approval
Conformity
CE
Approval
UR
Protection of persons and equipment
Enclosure
Thermal contact
Design
Switching capacity
Environmental conditions
Climate
Storage
Transport
Operation
Site altitude
Vibration resistance
2
(9.81 m/s
= 1 g)
42
2006/95/EC
Low−Voltage Directive
UL508
Industrial Control Equipment, Underwriter
Laboratories (File−No. E232497) for USA and Canada
EN 60529
IP65
NEMA 250
Protection against contact to type 4
NC contact, 230 °C
250 V AC / 5 A
IEC/EN 60721−3−1
1K3 (−25 ... +60 °C)
IEC/EN 60721−3−2
2K3 (−25 ... +70 °C)
IEC/EN 60721−3−3
3K3 (−10 ... +55 °C)
Current derating from +45 ... +55 °C: 2.5 %/°C
0 ... 4000 m amsl
1000 ... 4000 m amsl: Current derating 5 %/1000 m
EN 50178,
Acceleration resistant up to 1 g
IEC 61800−5−1,
Germanischer
Loyd, general
conditions
l
EDKRBS047R DE/EN/FR/ES/IT 8.0