Gas Feeding Line - Riello RS 25/M BLU Instrucciones De Instalación, Funcionamiento Y Mantenimiento

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

(A)
6
4
1
2
3
L1
(B)
BURNERS AND RELATIVE GAS TRAINS APPROVED ACCORDING TO REGULATION
EN 676
GAS TRAINS L
Code
Model
**
MB-DLE 405
3970500
3970553
MB-DLE 407
*
3970229
3970554
MB-DLE 410
*
3970230
3970144
MB-DLE 412
*
3970231
3970180
MB-DLE 415
*
3970232
3970181
*
3970233
MB-DLE 420
3970182
*
3970234
*
Trains complete with 6-pin plug for connection to burner.
**
Replace the 6-pin plug with the one supplied with the burner, in accordance with
the wiring diagram on page 25.
(C)
9
7
P1
P2
5
L
BURNER
Ø
C.T.
RS 25/M RS 35/M
3/4"
-
3/4"
-
1"
-
1"1/4
-
1"1/2
-
-
-
2"
D3839
10
8
11
D3791
7
11
Code
Code
-
3010123 3000824
3010123 3000824
3010123 3000824
3010123
-
3010123
-
3010123
3010123
3000822
-
-
8

GAS FEEDING LINE

• The gas train must be connected to the gas
attachment 1)(A), using the flange 2), gasket
3) and screws 4) supplied with the burner.
• The gas train can enter the burner from the
right or left side, depending on which is the
most convenient, see fig. (A).
• The gas solenoids must be as close as possi-
ble to the burner, to ensure that the gas
reaches the combustion head within the safety
time of 3s.
• Make sure that the pressure governor calibra-
tion range (colour of the spring) includes the
pressure required by the burner.
GAS TRAIN (B)
Approved, together with the burner, according to
the regulation EN 676, and supplied separately
from the burner, with the code indicated in the
table (C).
KEY (B)
1 - Gas input pipe
2 - Manual valve
3 - Vibration damping joint
4 - Pressure gauge with pushbutton cock
5 - Multibloc, including:
- filter (replaceable)
- working valve
- pressure adjuster
6 - Minimum gas pressure switch
7 - Valve seal checking device.
In accordance with the standard EN 676,
gas valve leak detection control devices
are compulsory for burners with maximum
outputs of more than 1200 kW.
8 - Gasket
9 - Gas adjustment butterfly valve
10 - Max gas pressure switch (accessory)
11 - Gas train/burner adaptor
P1 - Pressure at combustion head
P2 - Up-line pressure of valves/adjuster
P3 - Pressure up-line from the filter
L - Gas train supplied separately with the code
indicated in table (C)
L1 - The responsibility of the installer
KEY TO TABLE (C)
C.T.= Checking device for gas valves seal:
- = Gas train without gas valve leak
detection control device; device that
can
be
ordered
assembled subsequently (see Col-
umn 7).
♦= Train with seal checking device
already assembled.
7
= Valve seal checking device VPS.
Supplied separately from gas train on
request.
11 = Gas train/burner adaptor.
Supplied separately from gas train on
request.
Note
See the accompanying instructions for the
adjustment of the gas train.
separately
and

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Rs 35/m blu39105103910511391061039106113910640 ... Mostrar todo

Tabla de contenido