Operation (Special Conditions)
OPERATION ON OVERLOAD
When the UPS detects an output overload, it will commence a countdown (the length of time depending on the severity of the overload).
If the UPS is still overloaded at the end of the countdown, the UPS will automatically shut down and go into Bypass Mode.
Overload Condition
LCD Display Message
102% - 125%
OVERLOAD 102%
LOAD=XXX% X.XXKW
125% - 150%
OVERLOAD 125%
LOAD=XXX% X.XXKW
>150%
OVERLOAD 150%
LOAD=XXX% X.XXKW
BATTERY CHARGE WARNINGS
Since your UPS can provide battery backup only for as long as the batteries remain charged, these warnings should be acted on immediately.
Battery Charge Warning
Battery charge nearly depleted
Low battery shutdown

OPERATION UNDER SHUTDOWN

Your UPS will shut down and the LCD will display a message if it detects one of the following conditions. Note: For all conditions, the
"Input," "Output" and "Bypass" LEDs will be illuminated.
Condition
Extended Overload (>150%)
Output Short Circuit
Remote Shutdown Command
(from DB9 interface)
Remote Shutdown Command
(from RJ11 interface)
Internal Faults
Countdown to Shutdown
1 minute
30 seconds
2 seconds
LCD Display Message
BATTERY LOW
LOW BATTERY! SHUT DOWN...
LCD Display Message
OVERLOAD XX%
SHUT DOWN...
SHORT CIRCUIT!
SHUT DOWN...
REMOTE
SHUT DOWN...
EMERGENCY STOP!
SHUT DOWN...
INVERTER TOO LO
SHUT DOWN...
INVERTER TOO HI
SHUT DOWN...
DC BUS +/- HIGH/LOW
SHUT DOWN...
OVER TEMPERATURE
SHUT DOWN...
11
(continued)