Indoor Unit Drain Piping - LG CEILING CASSETTE Manual De Instalación

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

THE INDOOR UNIT INSTALLATION
8
Hanging bolt
(W 3/8 or M10)
Nut
(W 3/8 or M10)
Spring washer
(M10)
The following parts is option.
① Hanging Bolt
- W 3/8 or M10
② Nut
- W 3/8 or M10
③ Spring Washer - M10
④ Plate Washer - M10
Drill the piping hole on the wall slightly tilted to the outdoor side using a Ø 70 hole-core drill.
CAUTION
!
Tighten the nut and bolt to prevent unit
falling.
Wall
Indoor
Keep the length of the bolt
from the bracket to 40 mm
Flat washer for M10
(accessory)
Ceiling board
Flat washer for M10
(accessory)
Nut
(W 3/8 or M10)
Adjust the
same height
Outdoor
Ceiling
Air Conditioner body
Keep the length of 15~18 mm
between the air conditioner
bottom surface and the ceiling
surface
Set screw of
Paper model
paper model (4 pieces)
for installation
Open the ceiling board
along the outer edge of the
paper model

Indoor Unit Drain Piping

- Drain piping must have down-slope (1/50 to
1/100): be sure not to provide up-and-down
slope to prevent reversal flow.
- During drain piping connection, be careful
not to exert extra force on the drain port on
the indoor unit.
- The outside diameter of the drain connection
on the indoor unit is 32 mm.
Piping material: Polyvinyl chloride pipe
VP-25 and pipe fittings
- Be sure to execute heat insulation on the
drain piping.
- Install the drain raising pipes at a right
angle to the indoor unit and no more than
300 mm from the unit.
Pipe clamp
Indoor unit
Maintenance
drain port
300 mm or less
Ceiling
board
Upward
routing
not allowed