300 mm or less
300 mm or less
300 mm or less
Clamp metal(attached)
Heat insulation material: Polyethylene
foam with thickness more than 8 mm.
Drain test
The air conditioner uses a drain pump to drain
water.
Use the following procedure to test the drain
pump operation:
- Connect the main drain pipe to the exterior
and leave it provisionally until the test comes
to an end.
- Feed water to the flexible drain hose and
check the piping for leakage.
- Be sure to check the drain pump for normal
operating and noise when electrical wiring is
complete.
- When the test is complete, connect the
flexible drain hose to the drain port on the
indoor unit.
Feed
water
Drain Pump
Drain pan
CAUTION
!
The supplied flexible drain hose should not
be curved, neither screwed. The curved or
screwed hose may cause a leakage of
water.
Max 300 mm
Metal
clamp
Insulation
1 -1.5 m
Drain raising pipe
Drain hose(attached)
Flexible drain hose
(accessory)
Main
drain pipe
Drain
Glue the joint
port
Drain hose connection
Use the clip (accessory)
Hanger
distance
Hanger Bracket
1~15 m
1/50~1/100 slope
Flexible drain hose
THE INDOOR UNIT INSTALLATION
HEAT INSULATION
- Use the heat insulation material for the
refrigerant piping which has an excellent
heat-resistance (over 120 °C).
- Precautions in high humidity circumstance:
This air conditioner has been tested
according to the "KS Standard Conditions
with Mist" and confirmed that there is not
any default. However, if it is operated for a
long time in high humid atmosphere (dew
point temperature: more than 23 °C), water
drops are liable to fall. In this case, add heat
insulation material according to the following
procedure:
Indoor
unit
- Heat insulation material to be prepared...
Adiabatic EPDM or NBR with thickness 10 to
20 mm.
- Stick glass wool on all air conditioners that
are located in ceiling atmosphere.
Wiring Connection
- Open the control box cover and connect the
Remote controller cable and Indoor power
wires.
- Remove the control box cover for electrical
connection between the indoor and outdoor
unit. (Remove screws ①)
- Use the cord clamper to fix the cord.
Connection
cord
between the
1
indoor unit and
the outdoor
unit
9
Fastening band
(accessory)
Refrigerant
piping
Thermal insulator
(accessory)
Remote
controller
cable
1
Control box cover
(On which the
Electric Wiring
Connection is put)