P0010
Start Quick Commissioning
1 = Quick
P0010 must always be set back to '0'
Commissioning
before operating the motor. However if
P3900 = 1 is set after commissioning this
is done automatically
P0100
Operation for Europe / N. America
0 = kW / 50 Hz
For setting 0 and 1 use DIP Switch 2.
1 = hp / 60 Hz
For setting 2 use P0100
2 = kW / 60 Hz
P0304
Rated Motor Voltage
10 V - 2000 V
Nominal motor voltage (V) from rating
plate
P0305
Rated Motor Current
0 ... 2 * I nom
Nominal motor current (A) from rating
plate
P0307
Rated Motor Power
0 kW - 2000 kW
Nominal motor power (kW) from rating
plate. If P0100 = 1, values will be in hp
P0310
Rated Motor Frequency
12 Hz - 650 Hz
Nominal motor frequency (Hz) from
rating plate
12
Deutsch
Start Schnellinbetriebnahme
P0010 muss vor der Inbetriebnahme
des Motors auf '0' zurückgesetzt
werden. Wird nach der Inbetriebnahme
P3900 = 1 eingestellt, dann erfolgt dies
automatisch.
Betrieb für Europa / Nordamerika
Die Einstellungen 0 und 1 sind über
DIP-Schalter 2 herzustellen.
Einstellung 2 über P0100
Motornennspannung
Motornennspannung (V) vom
Typenschild des Motors
Motornennstrom
I nom = Motornennstrom (A) vom
Typenschild
Motornennleistung
Motornennleistung (kW) vom Typen-
schild. Bei P0100 = 1, sind die Werte
in hp
Motornennfrequenz
Motornennfrequenz (Hz) vom
Typenschild
MICROMASTER 430, Getting Started Guide 12/02