GENERAL METERING FEATURES AND FUNCTIONALITY
LCD
Error
Meter
Error
Category
Status
Message
None
NORMAL
None
Low
Warning
None
Current
Reverse
Err rC1 or
Installation
Energy
Err rC2
Bad
Err PF1 or
Installation
Power
Err PF2
Factor
Low
Err LU1 or
Installation
Voltage
Err LU2
Err HU1
Over
Installation
or Err
Voltage
HU2
Err HC1
Over
Installation
or Err
Current
HC2
Factory
FAIL 01
Failure
Service
FAIL 02 ...
Required
FAIL 05
Table 7 - LCD Indications
While in a failure condition, in addition to displaying a "FAIL" code on the error screen the
screen ID (leftmost digit) on every screen blinks, alternating between the screen ID and the
character "F".
For a single-element meter, no errors are reported on line 2.
If the meter reports an installation error, refer to Section 6 for troubleshooting. If the meter
reports a failure condition, contact Leviton technical assistance.
www.
L1/L2
Determination of
Bar/Arrow
Symbols
Error Condition
Animated arrow
No error or warning
Both off
pointing right
Bar and arrow
Blinking
Power greater than
indicators turned
(one or
or equal to -15W but
off
both)
less than +15W.
Blinking
Arrow pointing
Power less than
(one or
left (no blink)
both)
Checked only when
current is greater
Solid bar (no
Blinking
than starting current
blink), no arrow
(one or
level. Error when
either side
both)
phase angle is
greater than 80°
and less than 90°.
Solid bar (no
Blinking
blink), no arrow
(one or
Voltage below 102V.
either side
both)
Solid bar (no
Blinking
Voltage above
blink), no arrow
(one or
either side
both)
Current above 110A
Solid bar (no
Blinking
if configured for
blink), no arrow
(one or
100A CT or 220A if
either side
both)
configured for 200A
Blinking bar, no
Operational error
Both off
arrow either side
15
information@itm.com
.com
conditions.
-15W.
138V.
CT.
detected.