Testing The Installation; General Metering Features And Functionality; Mini Meter Display - Leviton MSTCT-2SC Manual Del Usuario E Instalación

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

1.800.561.8187
3
INSTALLATION INSTRUCTIONS
3.10

Testing the Installation

Verify Voltage:
Characters are always displayed on the LCD when the meter has proper power
on L1 and neutral (See Section 4.1 for a description of LCD screens).
Verify Energy:
Before checking energy direction, make sure there is a load drawing a minimum
of 1A connected to the meter.
The LCD has an energy-flow indicator in the lower left section of the display. The
energy-flow indicator points to the right when the meter measures positive energy
(normal) and points left when the meter measures negative energy.
If the arrow is not shown, points to the left or is shown with no pointer in either
direction, there is an installation problem. Refer to Section 6 for troubleshooting
instructions.
Verify Load:
The load LED has a 10Wh pulse rate (5 watt hours on, 5 watt hours off). The duty
cycle should be 50% when the meter is connected properly and a constant load
is applied. Figure 7 shows the appearance of the LCD when the meter is installed
properly.
Figure 7 - LCD Appearance in Proper Operation (Example)
4

GENERAL METERING FEATURES AND FUNCTIONALITY

4.1

Mini Meter Display

Mini meter LCD is shown below.
Main Numerical Display
Screen ID
Bar/
Arrow
Indicator
Table 5 shows the LCD screens in sequence at power up and during normal operation.
The startup screens are displayed only once at power up. From then on, the meter
repeatedly cycles through the runtime screens as described in Table 6. For dual-
element meters, energy, demand and power are shown on the runtime screens as
combined values for Line 1 and Line 2.
www.
k W h
L 1 L 2 H z
M A X
S U M
k W h
Line
Max
kWh
Demand
or kW
12
information@itm.com
.com

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Mini meter

Tabla de contenido