Fit the analogue I/O module:
1. Only in cases where the electronic module has been
removed: press the electronic module carefully into
the manifold base.
2. Check the seal and sealing surfaces and refit the sub-
base.
3. Place the screws so that the self-cutting threads are
used. Tighten the screws by hand in diagonally oppo-
site sequence. Tightening torque 0.9...1.1 Nm.
3.3 Setting the DIL switches
You can set the signal range of the relevant analogue chan-
nel with the 2-element DIL switches:
Signal range
Setting
0...10 V
0...20 mA
4...20 mA
Festo CPX-AX 0206NH English
DIL switch 0
DIL switch 1
0.1: OFF
1.1: OFF
0.2: OFF
1.2: OFF
(default)
(default)
0.1: ON
1.1: ON
0.2: OFF
1.2: OFF
0.1: OFF
1.1: OFF
0.2: ON
1.2: ON
0.1: ON
1.1: ON
0.2: ON
1.2: ON