Festo CPX-2A Serie Manual Del Usuario página 22

Ocultar thumbs Ver también para CPX-2A Serie:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 27
Input module CPX-2AE-U-I
(cont.)
Analogue inputs (cont.)
– Data on sensor selection
– Input resistance
– Permitted input voltage or
input current (destruction
limit)
Sensor supply
– Loading capacity
– Output voltage
– Fuses
– Response current
– Reaction after end of
overload
– Protection against incorrect
polarity at 24 V load input
– Protection against reverse
voltage
– Electrical isolation
– Between channel and
24 V
SEN
– Between the channels
22
Voltage inputs
Current inputs
≥ 100 kΩ
≤ 100 Ω (50 Ω)
30 V lasting
40 mA
One connection per input, the same
supply potential at all inputs, gener-
ated from 24 V
EL/SEN
Max. sum continuous current per
module: 0.7 A
24 V ± 25 %
Electronic, thermal
0.7...2.4 A
Can be parametrized
(see parameters)
Yes
Max. 30 V
The logic supply for the electrically
isolated analogue part is branched
from the analogue voltage
Yes (no potential isolation if internal
sensor supply is used)
No
Festo CPX-AX 0206NH English

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Cpx-2ae-u-iCpx-2aa-u-i

Tabla de contenido