Operating Limits:

Thermal carrier : Water
Water temperature : 5 ~65°C
Maximum water pressure : 16 bar
Air temperature : (as below)
Cooling Mode
Temperature
Minimum indoor
temperature
Maximum indoor
temperature
Minimum outdoor
temperature
Maximum outdoor
temperature
• The indoor unit is provided with air discharge and air intake "knock-out" hole for duct connection. However the connection of the
short duct for air discharge is possible on one side only.
• The use of short duct for air discharge will improve airflow distribution if there is an obstruction (such as a lighting fixture) or in
a long, narrow room or an L-shaped room. It is also use for air conditioning of two rooms simultaneously.
Possible Direction For Air Discharge And Air Intake
Air Discharge
Air Discharge
Note:
• Avoid using the short duct on which the air discharge grille can be completely closed, to prevent evaporator freezing.
• In order to prevent condensation forming, be sure that there is sufficient thermal insulation and no leakage of cool air when
installing the short duct.
• Keep the introduction of fresh air intake within 20% of total air flow. Also provide a chamber and use a booster fan.
Sealing Material
• It is possible to seal one of the four air discharge outlet. (Sealing two or more air discharge outlet could cause a malfunction.)
• Remove the front panel and insert the sealing material into the air discharge outlet on the indoor unit to seal the air outlet.
• The sealing material is the same length as the longer air discharge outlet. If it is desired to seal the shorter air discharge outlet, cut
the sealing material to shorten it.
• Push the sealing material in about 10mm beyond the bottom surface of the indoor unit so that it does not touch the air louver.
• Be sure not to push the sealing material in any further than about 10mm.
If there is a power cut when the unit is operating, it will automatically resume the same operating mode when the power is restored.
(Applicable only to units with this feature.)

OPERATING RANGE

Ts °C/°F
Th °C/°F
16.0 / 60.8
11.0 / 51.8
32.0 / 89.6
23.0 / 73.4
16.0 / 60.8
-
46.0 / 114.8
-

ACCESSORY PARTS

Air Discharge
Air Intake
Air Discharge

AUTO RANDOM RE-START FUNCTION

Heating Mode
Temperature
Minimum indoor
temperature
Maximum indoor
temperature
Minimum outdoor
temperature
Maximum outdoor
temperature
Ts: Dry bulb temperature.
Possible Opening Dimension For Duct Connection
50
50
50
10
115
20
Air Discharge Knock Out Hole
6
Ts °C/°F
Th °C/°F
16.0 / 60.8
-
30.0 / 86.0
-
-5.0 / 23.0
-6.0 / 21.2
24.0 / 75.2
18.0 / 64.4
Th: Wet bulb temperature.
50
50
10
115
Air Intake
Knock Out Hole
PCD Ø140
Ø100