Madas ITG Serie Manual De Instrucciones página 18

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

7.0 - ACTUATOR- LM230ASR
Damper actuator for operating air control dampers in ventilation
and air-conditioning system for building services installations
• For air control dampers up to approx. 1 m
• Torque 5 Nm
• Nominal voltage AC 100... 240 V
• Control: modulating DC 0 ... 10 V, position feedback DC 2 ... 10 V
7.1 - TECHNICAL DATA
The damper actuator is not allowed to be used outside the specified field of application, especially in aircraft or any
other form of air transport.
• Assembly must be carried out by trained personnel. Any legal regulations or regulations issued by authorities must
be observed during assembly.
• The device may only be opened at the manufacturer's site. It does not contain any parts that can be replaced or
repaired by the user.
• The cable must not be removed from the device.
When calculating the required torque, the specifications supplied by the damper manufacturers (cross section,
design, installation site), and the air flow conditions must be observed.
ITG
2
18
Madas Technical Manual - 9|9.2 - REV. 0 of 12
Feb 2019
th

Publicidad

Tabla de contenido
loading

Tabla de contenido