Adjusting Gas Pressure At The Nozzles - Sime Brava Slim 40 BF Manual De Instalación Y Mantenimiento

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

– press the button
>
once again to make the boiler operate at
maximum power. If the gas pressure values are correct it is
possible to determine the combustion data and take a reading
of the combustion efficiency as provided for by legislation in
force
– press the button
y
Procedure". The boiler water delivery temperature will
appear on the display
– close the taps opened previously and check that the appliance
shuts down
– disconnect the pressure gauges, carefully close the pressure
points (6) and (7), put the control panel back to the original
position and refit the front panel (2).
Gas supply pressure
Type of gas
G20
Pressure (mbar)
20
Installation with SPLIT PIPE SYSTEM smoke outlet
Heat
Model
Output
Max
Brava Slim 40 BF
min
Installation with CONCENTRIC smoke outlet
Heat
Model
Output
Max
Brava Slim 40 BF
min
If the gas pressure values are different from the values indicated
in the table, adjust the gas nozzle pressure as described in the
section below.
3.6.2

Adjusting gas pressure at the nozzles

m
CAUTION
Considering that:
– the front panel (2) has already been removed and
the point (6) is connected to the pressure gauge
– the main system switch must be set to "ON"
– the gas supply must be open
– there must be no current requests for heat
("Summer" mode
"Winter"
n
with air thermostats open)
– the adjustments described below must be carried out
in sequence.
94
to exit the "Chimney sweeper
G30
G31
28-30
37
Pressure at nozzles (mbar)
G20
G30
G31
10,4 - 10,8
26,8 - 27,2
34,8 - 35,2
0,5 - 0,8
1,2 - 1,5
2,0 - 2,3
Pressure at nozzles (mbar)
G20
G30
G31
11,2 - 11,6
26,8 - 27,2
34,8 - 35,2
0,8 - 1,1
2,4 - 2,7
2,9 - 3,2
l
with hot water valve closed or
Adjusting maximum gas pressure:
– press button
r
and set the DOMESTIC HOT WATER SET to
maximum using the button
– press and hold down the buttons
for approximately 6 seconds until the message "MA" appears
on the display alternating with "nu"
– open one or more than one hot water tap
– the boiler will start up and the message "P01" will appear on
the display (Adjusting maximum gas pressure)
– press the buttons
>
or
<
until the pressure value indicated in
the table appears on the pressure gauge
– once the value indicated in the table has been reached, press
the button
y
for approximately 2 seconds to confirm the
value which will then flash once.
Adjusting minimum gas pressure:
– press the button
r
twice, the message "P00" will appear on
the display
– press the buttons
>
or
<
until the pressure value indicated in
the table appears on the pressure gauge
– once the value indicated in the table has been reached, press
the button
y
for approximately 2 seconds to confirm the
value which will then flash once.
– press and hold down the buttons
time for approximately 6 seconds until the water delivery
temperature appears on the display and the boiler shuts
down/starts up
– close the valves which were opened previously.