Test I: Runs But Does Not Cool Properly
Series DE/EV0041, Series DE/EV0061, DC0061
Complete the "Diagnostic Pre-Checks."
Remove refrigerator from enclosure,
but keep power supplies connected.
Inspect condenser coil for restriction.
YES
Is it
restricted?
NO
Set thermostat to "5." Is the
condenser fan working?
NO
Check for 12 VDC at terminal (+) on
the control module.
YES
Is voltage
correct?
NO
Replace control module.
Remove restriction. Clean as needed.
YES
Fan has failed. Replace cooling unit.
Fan has failed. Replace cooling unit.