Tripp-Lite SmartOnline 7.5kVA Manual Del Propietário página 10

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Optional Connection
Contact-Closure Communication Connection
Use a user-supplied contact-closure DB9 cable
ule's Dry-Contact port to the communication port on your computer or other
equipment. This will allow basic contact-closure signals to be sent to and from
the UPS. Refer to diagram
this port. Install on your computer the Tripp Lite PowerAlert Software appro-
priate to your computer's operating system.
DRY CONTACT INTERFACE DIAGRAM
LOW BATTERY
BACK-UP
NO
COM
NC
5
4
3
2
1
9
8
7
6
SIGNAL FROM COMPUTER
MAXIMUM CAPACITY OF DRY CONTACT: AC250V/3A • DC30V/3A
1c
EPO Port Connection
2
This optional feature is only for those applications which require connection
to a facility's Emergency Power Off (EPO) circuit. When the power module is
connected to this circuit, it enables emergency shutdown of the output. Using
the included cable
plied remote switch. The pin assignments for the EPO port are shown in dia-
gram
. Note: if there is a short between pins 2 and 3, 2 and 5, 4 and 5, or 3
2b
and 4, the UPS system will power off.
Internal SNMP/WEB Card Insertion
3
Remove the small cover panel from the accessory slot to use optional acces-
sories to remotely monitor and control your UPS. Contact Tripp Lite Customer
Support at (773) 869-1234 for more information, including a list of available
SNMP, network management and connectivity products.
Manual Bypass Operation
The UPS system includes a self-contained power/battery module along with an independ-
ent, detachable PDU with a bypass switch. This switch allows qualified service personnel
to remove the detachable PDU from the power/battery module for routine maintenance
without disrupting power to connected loads. While this switch is set to "BYPASS", con-
nected equipment will receive unfiltered AC utility power, but the equipment will not
receive battery power in the event of a blackout.
Note: If desired, an optional hardwire detachable PDU is also available separately from
Tripp Lite. Contact Tripp Lite for details.
WARNING! For qualified service personnel only. Failure to follow the bypass proce-
dure completely will not adequately power down the UPS power/battery module,
resulting in the continued risk of death or injury from potential contact with high
voltage. The UPS's power/battery module and detachable PDU are extremely heavy.
This procedure requires several people to perform.
UPS Power/Battery Module Removal
STEP 1. Disable PowerAlert Software and disconnect communication cables from the
communication ports
STEP 2. Press UPS's "OFF" Button
see a "BYPASS MODE" message shown in the LCD Display
STEP 3. Turn the detachable PDU's Bypass Switch
STEP 4. If an external battery module is connected to the UPS
The UPS power/battery module is now safely powered down and it can be detached
from the PDU to perform maintenance/replacement.
1c
and table
1d
to determine the signals carried by
DRY CONTACT INTERFACE TABLE
lm in. > 3.3 mA
UPS
Operating
REMOTE SHUTDOWN SIGNAL
FROM EXTERNAL
NO
Mode
COM NC
Normal
Back Up
Low Battery CLOSE CLOSE
>2 sec
Fault
12 V
* Inactive: may be in either state
0
2a
, connect the power module's EPO port to a user-sup-
on the UPS power/battery module.
A
, if the UPS is powered, until you hear a beep and
C
B
continued
B
to connect the power mod-
Pin 8,3 Pin 1,3 Pin 6,3
OPEN
OPEN
*
CLOSE
*
*
*
*
*
CLOSE
1d
(for power module maintenance or replacement)
.
D
to "BYPASS".
, disconnect it from the UPS.
E
10
2a
EPO PIN ASSIGNMENT
12V
X
1K
X
2b
3
A
E
Steps 1, 3 & 4
I/P
BYPASS
BATTERY
AC/DC
DC/AC
D
ON
MUTE
SELECT
SETUP
Step 2
1
2
3
4
5
6
B
O/P
C
OFF

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Smartonline 10kvaSmartonline single-phase 7.5kvaSmartonline single-phase 10kva

Tabla de contenido