Connection
Hardwiring Cautions
• Wiring must be done by a qualified electrician.
• When making wiring connections, observe the cable connection regulations appropriate to your area [e.g. National Electrical Code (NEC)
in the U.S.] at all times. Be sure to install an easily accessible disconnect switch in your installation wiring so you may cut off the UPS's
AC input during fires and other emergencies. Ensure that cables are fitted with cable sleeves and are secured by connector clamps. Tighten
connections with a torque of not less than 24-28 inch-pounds (2.7-3.2 NM).
• Make sure that your equipment is properly grounded.
• Using cables of improper size may damage your equipment and cause fire hazards. Choose appropriate cabling and protection circuits to
make wiring connections (Ground conductors must be the same size and type as the power conductors used):
200 - 240 (1Ø, 2-Wire + PE)
7.5kVA Models
10kVA Models
Connecting Modules to Each Other and to Utility Power and Equipment
Attach the PDU to the Power Module and Battery
1
Module.
Align and connect the PDU's power module input terminals with the terminals
on the back of the Power Module. Secure the PDU to the Power Module with
four screws
A
. Before proceeding further, ensure that the Bypass Switch is set
to NORMAL. Remove the utility input terminal block cover
2
Hardwire the PDU to a Utility Power Source.
Pass a user-supplied cable through the knockout on the left side of the PDU
C
and connect it to the PDU's input terminals
cover. Connect the other end of the cable to a utility power source.
Connect the battery module to the power module.
3
Consult the owner's manual that came with your battery module. Fully insert
the connector on the end of the battery module's cable
on the rear panel of the power module
mal. NOTE: the power module does not contain internal batteries and will not
start until a battery module is connected. The battery modules are fully charged
prior to shipping. However, before expecting full backup capability (particularly
if the battery module has been stored for an extended period) after the UPS system
is connected to a utility power source, allow the battery module to recharge for
12 hours. Once the UPS system is in use, it will charge the batteries and maintain
the charge level automatically. If needed, connect additional battery modules
in a daisy-chain with each module's cable inserted into the previous module's
connector
G
.
Contacts on Power/Battery Module
WARNING! High Voltage!
Risk of electrical shock!
Due to the presence of high voltage internal
batteries, even without AC present, these
contacts are live!
Do not let these contacts touch any surface!
Power ON
4
Turn UPS inverter ON: Press the UPS's "ON" Button
beep to begin inverter operation. Your UPS will perform a brief self-test and
show the results on the LCD Display
"Operation" section for the display sequence.
RATED INPUT CURRENT
30A 8 AWG (10mm
2
)
2
50A 6 AWG (16mm
)
. Small sparks may occur; this is nor-
F
Contacts on Detachable PDU
WARNING! High voltage!
Risk of electrical shock!
If AC is present and Bypass Switch is set to
"Bypass", these contacts are live!
Do not let these contacts touch any surface!
. See "Startup Self-Test" in the
H
RATED OUTPUT CURRENT
200 - 240V (1Ø, 2-Wire + PE)
30A 8 AWG (10mm
2
)
2
50A 6 AWG (16mm
)
B
.
D
. Replace the terminal block
E
into the connector
until you hear a
I
8
RATED OUTPUT CURRENT
120V (1Ø, 2-Wire + PE)
2 × 30A 8 AWG (10mm
2
)
2
2 × 50A 6 AWG (16mm
)
A
1
C
2
F
G
E
3
I/P
BYPASS
BATTERY
AC/DC
DC/AC
I
J
ON
MUTE
SELECT
SETUP
4a
OUTPUT PROTECTION
CIRCUIT
30A
63A
B
D
O/P
H
K
OFF