14.2 Examples of refrigerant system address
setting
Ex.
Indoor unit
Outdoor unit
1
PEH-P8·10MYA
–
2
PEH-P16·20MYA
No.1
No.2
* Set the refrigerant system address of one outdoor unit to 00 for the power supply
to the remote controller.
(The refrigerant system address is set to 00 when shipped from the factory.)
Do not duplicate the refrigerant system address settings within the same system.
14.3 Capacity control setting method (PEH-
P16·20MYA only)
With the PEH-P16·20MYA which has two outdoor units, the capacity can be con-
trolled to 0%, 50% or 100%.
This is set by setting the outdoor unit side dip switches as shown in the table below
before turning the power on.
No.1 side outdoor unit
No.2 side outdoor unit
DipSW5-1
OFF
24
Outdoor unit refrigerant
Remote controller
system address
power supply unit
00
00
✕
01~15
ON