Installation
Programming
Vive PowPak Phase Select Dimming module -
additional options available through the Vive app
Part of the Vive Family
Start Here
Programming with a Vive Hub
The Vive hub can be set-up easily with any Wi-Fi enabled iOS
1
Android
compatible device.
®
A
Download the Lutron Vive app.
B
Open the app and follow the instructions.
vive.lutron.com
X
Note: For further information on set up, programming, and
troubleshooting with a Vive system, please refer to the installation
instructions included with the Vive hub or visit www.lutron.com/vive
Note: For programming the PowPak module without a Vive hub
see reverse side.
Programming without a Vive Hub
Associate Wireless Transmitters to
1
PowPak module
Before beginning this step, make sure that there are no other Vive
devices being set up within the same building. It is possible that
wireless transmitters from other systems can be incorrectly associated
to this PowPak module.
A
Enter association mode. On PowPak
module, hold Toggle button " u " for
RMJS-PNE-DV
6 seconds until lights flash.
120 / 277 V~ 50 / 60 Hz
The indicator LED will begin
flashing twice per second.
50019498a
B
Hold the indicated button on each transmitter for 6 seconds. Lights
will flash to show that wireless transmitters have been associated.
Link
C
On PowPak module, hold Toggle button " u " for 6 seconds
to save association. Lights will flash and LED will quickly blink
for 2 seconds. NOTE: PowPak module will automatically exit
association mode 10 minutes after the last activity. However,
devices will be unresponsive until the timeout has occurred.
D
Permanently install wireless transmitters (consult individual
component installation guides for information).
Lutron, PowPak, Pico, Hi-lume, Radio Powr Savr, and Vive are trademarks or registered trademarks of Lutron Electronics Co., Inc. in the US and/or other countries. Safari is a trademark of Apple Inc., registered in the U.S. and other countries. All other product names, logos, and brands are property of their respective owners.
©2013 – 2021 Lutron Electronics Co., Inc.
Calibrate the Radio Powr Savr Daylight Sensor
2
Daylight Sensor will control all wired fixtures equally.
A
Initiate calibration process. Press and release the "Cal." button on the Daylight Sensor.
B
Set lights in room to desired light level using Raise / Lower buttons "▲ / " buttons on a
Pico remote or the PowPak module.
C
Press and hold the "Cal." button for 6 seconds.
D
Exit room for 5 minutes to complete calibration.
Note: When calibration has completed, all lights will flash and begin to respond to daylight.
Multiple Daylight Rows (Optional)
or
®
For every row of daylighting, a separate PowPak module must be used. For detailed setup refer to the tuning section of
the Radio Powr Savr Daylight Sensor installation guide.
• Select the PowPak module that you want to adjust by pressing the toggle button.
Set a Favorite Light Level
3
For Pico remote controls with a Favorite Button.
A
Adjust lights to desired level:
Use the Raise button "
" or Lower button "
B
Save favorite level:
Press and hold the Favorite button for 6 seconds. The load will flash 3 times to
confirm that the Favorite level is saved.
Set Low-End Trim and High-End Trim
4
For best results, minimize the amount of sunlight entering the room before performing the following procedures.
Notes:
Depending on the fixture manufacturer or load, low-end trim and high-end trim may need to be
adjusted.
• Trim low-end to ensure a stable light level because some loads will flicker or drop out if trimmed
too low.
• Be sure that you can turn on the lights to the low-end trim level without any abnormal operation.
• The factory default high-end trim is suitable for most applications but can be adjusted as desired.
Low-End Trim
A
Enter low-end trim adjustment mode:
Press and hold the Lower button " " on the fixture control for 12 seconds.
The lights will flash and the indicator LED will begin flashing.
B
Adjust the low-end trim:
Use the Raise button "▲" and Lower button " " on the fixture control to adjust and set the lights to the desired low-end
lutron.com
(1 to 45%).
C
Save the low-end trim:
Press and hold the Toggle button " u " for 6 seconds to save setting.
The indicator LED will begin flashing and then turn solid to indicate new level has been saved.
High-End Trim
A
Enter high-end trim adjustment mode:
Press and hold the Raise button "▲" on the fixture control for 12 seconds. The lights will flash and the indicator LED will flash.
B
Adjust the high-end trim:
Use the Raise button "▲" and Lower button " " on the fixture control to adjust and set the lights to the desired high-end
(55 to 100%).
Cal.
C
Save the high-end trim:
Test
Press and hold the Toggle button " u " for 6 seconds to save setting. The indicator LED will begin flashing and then turn
solid to indicate new level has been saved.

Error Codes

The LED on the PowPak module will flash when certain load limitations are exceeded.
LED Sequence
LED flashes 1 time then turns off for
4 seconds
LED flashes 2 times then turns off for
3 seconds
LED flashes 3 times then turns off for
2 seconds
LED flashes 4 times then turns off for
1 second
Link
Cal.
Test
(Optional)
Raise
" on the Pico remote control.
Favorite
(Optional)
RMJS-PNE-DV
120 / 277 V~ 50 / 60 Hz
50019498a
Error Mode
Example
Shorted FET detection mode
When an MLV transformer saturates
Over Voltage
If an MLV load is used in
Protection mode (OVP)
reverse-phase
Excessive inrush current from
Over Current Protection
drivers/ballasts that don't comply
mode (OCP)
with NEMA 410
Over Temperature
Exceeding rated load
Protection mode (OTP)
Set Minimum Light Level
5
(Optional)
Certain applications (e.g., hallways), may require that the lights never turn off. For these areas, activate Minimum Light
Level mode.
A
Enter minimum light level adjustment mode:
Press and hold Toggle button " u " and Lower button " " for 12 seconds. Lights will flash high-low-high and LED will
begin flashing.
If lights stop flashing and go to high-end, the minimum light level is set to OFF (default).
If lights stop flashing and go to low-end, the minimum light level is ON and set to low-end.
B
Change the minimum light level:
Press Raise button "▲" to set minimum light level to low-end.
Press Lower button " " to set minimum light level to OFF.
C
Save the minimum light level:
Press and hold Toggle button " u" for 6 seconds. LED will quickly flash to indicate that new level has been saved.
Lower
Set Occupancy Light Levels
6
Note: Unoccupied light level is always the minimum light level and cannot be adjusted.
A
Set desired occupancy light levels:
Use Raise / Lower buttons "▲ / " on the PowPak module or Raise / Lower buttons "
remote controls.
B
Save occupancy light levels:
Press and hold Test button (or Lights On button) for 6 seconds on any associated Radio Powr Savr occupancy sensor.
Release when sensor lens starts to flash.
Or, press and hold Lights On button for 6 seconds on any associated Radio Powr Savr occupancy sensor. Release when
sensor lens starts to flash.
lutron.com
FCC/ IC Information:
This device complies with part 15 of the FCC Rules and Industry Canada license-exempt RSS standard(s). Operation is subject to the
following two conditions:
(1) This device may not cause interference, and
(2) this device must accept any interference, including interference that may cause undesired operation. Modifications not expressly
approved by Lutron Electronics Co., Inc. could void the user's authority to operate this equipment.
Note: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC
Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment
generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause
harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If
this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and
on, the user is encouraged to try to correct the interference by one or more of the following measures:
•Reorient or relocate the receiving antenna
•Increase the separation between the equipment and receiver
•Connect the equipment into an outlet on a circuit different from that to which the receiver is connected
•Consult the dealer or an experienced radio/TV technician for help
Customer Assistance:
U.S.A. / Canada: 1.844.LUTRON1
www.lutron.com/support
Limited Warranty: www.lutron.com/TechnicalDocumentLibrary/369-119_Wallbox_Warranty.pdf
(Optional)
/
" on all associated Pico
Mexico: +1.888.235.2910
Central / South America: +1.610.282.6701

Publicidad

loading

Este manual también es adecuado para:

Vive powpak rmjs-pne-dv-em