Installation and debugging
SW01
SW02
Forced heat alternating display "HHH" (according to Start 5 seconds to enter, all the internal
1
F
mechanism of hot running, press Stop to exit for 5 seconds).
2
0-F
Communication shows the program version (1 decimal), or "---"
The machine type: (0:common indoor machine; 1:wall hanging; 2:Fresh air machine ;
3
0-F
3:heat exchanger, 4/5/6/7:common indoor machine).
4
0-F
If there is a failure to show the internal fault code, otherwise, "---"
5
0-F
Indoor machine capability (1 decimal)
First and the second: indoor machine current mode of operation, (00: off, 01: air supply, 02: cooling,
6
0-F
03: dehumidification, 04: heating) , the third: external machine capacity requirements (0: No, 1: Yes)
7
0-F
Indoor machine PMV opening (unit: pls, maximum display 999)
Indoor unit of air conditioner:
First: float switch (0- disconnect, 1- closed)
8
0-F
Second place: water pump (0- closed, 1- open)
Third place: electric heating (0- closed, 1- open)
(110 float switch is closed, the water pump is opened, the electric heating off)
9
0-F
Indoor machine TA: ambient temperature value (unit: Celsius)
A
0-F
Indoor TC1: air temperature value (unit: Celsius)
B
0-F
Indoor machine TC2: liquid pipe temperature (unit: Celsius)
C
0-F
Indoor machine motor: room running wind speed (0- stop, 1- low wind, 2- stroke, 3- high wind)
2. Supercooling valve plate module parameter display
SW01
SW02
0
Over cooling valve plate failure code (cold plate module sent)
1
Super cooled valve plate program version (1 decimal)
2
Target opening of the expansion valve of the supercooling valve plate(unit: pls, max: 999)
3
The current opening of the expansion valve of the cold valve plate (unit: pls, max: 999)
4
Tc1 temperature of supercooling valve plate (unit: Celsius)
D
5
Tc2 temperature of supercooling valve plate (unit: Celsius)
6
Set aside (display "---")
7
Set aside (display "---")
8
Set aside (display "---")
9
Set aside (display "---")
Seven segment digital tube display content
Seven segment digital tube display content
18