3.4 Connecting sensors (PNP inputs)
For connecting sensors use cables of type KM12−DUO−...
or plugs of type SEA−GS−7, SEA−M12−5GS−PG7, SEA−
GS−11−DUO or SEA−5GS−11−DUO. Fasten the plug with the
aid of the union nut.
Seal the unused sensor connections (M12 sockets) with
protective cap type ISK−M 12. Only then is protection class
IP65 guaranteed.
Please note
The inputs are implemented on the basis of
IEC 1131−2 type 02.
The inputs are resistant to short circuits. If a short
circuit occurs, the slave will be switched off. The AS−
Interface regards this slave as being faulty. When the
short circuit is eliminated, the slave registers immedi
ately as capable of functioning.
1
Pin assignment of sensor
connection 1
1: 24 V
2: Input In−2
3: 0 V
4: Input In−1
Pin assignment of sensor
connection 2
1: 24 V
2: Input In−4
3: 0 V
4: Input In−3
18
2
3
1
4