 After one year of storage, connect the device to mains voltage for 60
minutes.
1.4 After unpacking
 Check if the delivered devices corresponds to the order.
 Check the device for transport damage and completeness.
GB
 Report any defects/damage to the supplier immediately.
1.5 Place of installation
In rooms without weather exposure.
Avoid direct sunlight exposure.
Avoid dust.
Keep away from strong electromagnetic fields.
Keep away from combustible material.
Provide sufficient cooling. Install fans when installing the frequency
inverter inside an enclosed cabinet.
Altitude of installation: ≤ 4000 m, above 1000 m with reduced power
(reduced output current).
Ingress protection rating of frequency inverter: IP20. Use of the device in
explosive atmospheres is not permitted.
The frequency inverter produces noise. For this reason it should be
installed in areas where usually people do not stay for a long time.
Noise emission in operation is < 85 dB(A) in the case of sizes 1 through 7.
Noise emission in operation is approx. 86 dB(A) in the case of size 8. Use
ear protectors when staying near the frequency inverter.

1.6 Operating conditions

 Size 1...7:
o Ambient temperature: 0...55°C, as from 40°C, power reduction of
2.5% / K should be considered.
 Size 8
o Ambient temperature: 0...55°C, as from 45°C, power reduction of
2.5% / K should be considered.
 Ambient pressure: 70 ... 106 kPa
 The frequency inverter may be operated in TN, TT and IT grid types.
Operation in a corner-grounded TN grid shall not be permissible.
 Environment specification: Pollution degree 2 and overvoltage category III
(IEC 60664-1 /DIN VDE 0110-1) up to 2000 m installation altitude. Above
2000 m installation altitude overvoltage category II.
62
Quick Start Guide ACU
10/18