1.3

Transport and storage

• Ambient temperature: -25 ... 55 °C
• Relative humidity: 5 ... 95%, no water condensation
• Store product in its original package in dust-free room.
• Avoid high temperatures.
• After one year of storage, connect the device to mains voltage for 60 minutes.
1.4

After unpacking

• Check if the delivered devices corresponds to the order.
• Check the device for transport damage and completeness.
• Any defects/damage must be reported to the supplier immediately.
1.5

Place of installation

• In rooms without weather exposure.
• Avoid direct insolation.
• Avoid dust.
• Not in the neighborhood of strong electromagnetic fields.
• Not in the neighborhood of inflammable material.
• Provide for sufficient cooling. Install a fan if the frequency inverter is installed in a closed electrical cabinet.
• Altitude of installation: ≤ 4000 m, above 1000 m with reduced power (reduced output current).
• Ingress protection rating of frequency inverter: IP20.
• The frequency inverter produces noise. For this reason it should be installed in areas where people normally
don't stay.
• Noise emission in operation is < 85 dB(A) in the case of sizes 1 through 7.
• Noise emission in operation is approx. 86 dB(A) in the case of size 8. Ear protectors must be used when staying
near the frequency inverter
• Use of the device in explosive atmospheres is not permitted.
1.6

Operating conditions

• Size 1...7:
o Ambient temperature: 0...55°C, as from 40°C, power reduction of 2.5% / K should be considered.
• Size 8
o Ambient temperature: -25...55°C, as from 45°C, power reduction of 2.5% / K should be considered.
• Relative humidity: 5 ... 85%, no water condensation
• Ambient pressure: 70 ... 106 kPa to be checked
• The frequency inverter may be operated in TN, TT and IT grid types.
Operation in a corner-grounded TN grid shall not be permissible.
• Environment specification: Pollution degree 2 and overvoltage category III (IEC 60664-1 /DIN VDE 0110-1).
• The frequency inverter may be connected to power supply every 60 s. If the unit is switched on more fre-
quently, it may be damaged. This must be considered when operating a mains contactor in jog operation mode.
• Max. permissible expected short circuit current at mains connection:
up to 132 kW device power (Size 7): 5 kA;
160...250 kW device power (size 8): 18 kA
as from 315 kW device power (size 8): 30 kA