Operating Conditions - BONFIGLIOLI Vectron AEC Guia De Inicio Rapido

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

WARNING
Repairs may only be carried out by the manufacturer or persons who are authorized by the
manufacturer.
Repairs must be carried out by qualified electrotechnical experts.
Do not modify the mains unit in any way not explained in this documentation.
Do not connect an inappropriate voltage supply.
Keep the manual accessible to the operators.
NOTE
For more information about the range of functions of the mains unit and about operation,
GB
maintenance and storage, refer to the supplied CD.
1.2
Proper use
The product is an electrical drive component. It is applicable for
installation in machines or electrical plants
industrial environments
1.3
Transport and Storage
Ambient temperature:-25 ... 55 °C
Relative humidity:
Store in original packaging in dry rooms without dust.
Avoid high temperature variations.
Connect to mains voltage for 60 minutes after one year of storage before use.
1.4
On opening the package
Make sure that the delivered product is the part you have ordered.
Check if the product is damaged and make sure that the delivery is complete.
Notify complaints to the supplier immediately.
1.5
Installation
Indoors , protected against weather influence.
Avoid direct sunlight exposure.
Avoid dust.
Keep away from strong electromagnetic fields.
Keep away from combustible material.
Provide sufficient cooling. Install fans when installing the frequency inverter inside an enclosed cabinet.
Altitude: ≤4000 m, over 1000 m with derating (output current reduction).
The degree of protection of the mains unit is IP20.
1.6

Operating conditions

Ambient temperature: 0 ... 40 °C
Relative humidity:
Ambient pressure:
During Standard operation leakage currents > 3.5 mA can occur.
26
5 ... 95%, free of condensation.
maximum 85%, free of condensation
70 ... 106 kPa
Quick Start Guide AEC
06/13

Publicidad

Tabla de contenido
loading