Permitted temperature differentials through the heat exchangers
○ Evaporator temperature differential ΔT = 3 ÷ 8°C with "Standard" set-ups. However, consider the minimum and maximum flow rates reported in the
tables "Water flow rate limits". The maximum and minimum temperature differentials for "Pump" set-ups are related to the performance of the pumps,
which must always be checked by means of the Up to Date selection software.
Evaporator water flow rate limits
Type of heat exchanger
m3/h
2335
m3/h
2365
m3/h
2405
m3/h
2465
m3/h
2515
m3/h
2565
m3/h
2645
m3/h
2705
m3/h
2755
m3/h
2805
m3/h
2865
m3/h
2935
m3/h
2995
m3/h
21075
m3/h
21115
m3/h
21275
Recovery water flow rate limits
Type of heat exchanger
m3/h
2335
m3/h
2365
m3/h
2405
m3/h
2465
m3/h
2515
m3/h
2565
m3/h
2645
m3/h
2705
m3/h
2755
m3/h
2805
m3/h
2865
m3/h
2935
m3/h
2995
m3/h
21075
m3/h
21115
m3/h
21275
Min
28
32
35
44
59
47
63
90
90
100
100
110
110
112
112
112
RC100
Min
Max
45
90
50
90
55
95
65
140
70
140
80
150
100
240
100
260
110
280
120
288
120
288
140
288
140
288
160
320
160
320
180
320
Shell and tube
48
EQS
Max
70
75
88
100
110
120
143
150
155
230
230
254
254
260
260
260