Technical parameters

Supply terminals:
Voltage range:
Power input max.
(apparent / loss):
Max. dissipated power
(Un + terminals):
Supply voltage tolerance:
Supply indication:
Time delay:
Time delay setting:
Illumination rang 1:
Illumination rang 2:
Control
Power the control input:
Load between S-A2:
Control. terminals:
Glow tubes connetions:
Max. amount of glow
lamps connected to
(230 V): max. amount 20 pcs (measured glow lamps
controlling input:
Impulse length:
Reset time:
Output
Number of contacts:
Current rating:
Breaking capacity:
Inrush current:
Switching voltage:
Output indication:
Mechanical life:
Electrical life (AC1):
Other information
Operating temperature:
Storage temperature:
Electrical strength:
Operating position:
Mounting:
Protection degree:
Sensor cable length:
Overvoltage category:
Pollution degree:
Max. cable size (mm
2
):
Dimensions:
Weight:
Weight of sensor SKS:
Standards:
SOU-1
A1 - A2
AC/DC 12 - 240 V
AC 230 V /
(AC 50 - 60 Hz)
50 - 60 Hz
AC 0.7 - 3 VA
DC 0.5 - 1.7 W
AC 12 VA / 1.8 W
3.5 W
-15 %; +10 %
green LED
0 - 2 min
potentiometer
1 - 100 Lx
100 - 50 000 Lx
0.8 - 530 mVA
yes
A1 - S
(UNI): no / (230 V): yes
(UNI): glow lamps cannot connected
with glow lamp 0.68 mA / 230 V AC)
min. 25 ms / max. unlimited
150 ms
1x changeover (AgSnO
)
2
16 A / AC1
4000 VA / AC1, 384 W / DC
30 A / < 3s
250 V AC1 / 24 V DC
red LED
3x10
7
5
0.7x10
-20 °C to +55 °C (-4 °F to 131 °F)
-30 °C to +70 °C (-22 °F to 158 °F)
4kV (supply - output)
any
DIN rail EN 60715
IP40 from front panel / IP20 terminals
max. 50 m (standard wire)
III.
2
solid wire max. 1x 2.5 or 2x 1.5 /
with sleeve max. 1x 2.5 (AWG 12)
90 x 17.6 x 64 mm (3.5˝ x 0.7˝ x 2.5˝)
(UNI): 76 g (2.7 oz.) / (230 V): 73 g (2.6 oz.)
15 g (0.5 oz.)
EN 60255-6, EN 61010-1
Function
Lx
ambient light
intensity
set level
A1-A2
TEST ON
S
15-18
Photosensor SKS
Sensor for SOU-1 is external and is connected to terminals IN.
Sensor is installable to panel (by screw-able transparent cover) to opening with diameter
16 mm. A part of the sensor is a plastic holder for placing into the wall or to another place.
Length of a line connector to the sensor cannot be more than 50 m. Doublecure cable can
be used as wire diameter min. 2x 0.35 mm
Protection degree is IP44. To keep this protection:
- photoresistor cover must be sealed by a rubber circle (part of the sensor)
- cable must be of round cross-selection
- the opening must be tight to the used cable
It is possible to use photoresistor, which changes resistance in accordance with
ambient illumination, as a sensor. Tolerance sensor ± 33 %.
light intensity
1 Lx
100 Lx
50 000 Lx
Warning
Device is constructed for connection in 1-phase AC 230 V or AC/DC 12- 240 V main
alternating current voltage and must be installed according to norms valid in the state of
application. Connection according to the details in this direction. Installation, connection,
setting and servicing should be installed by qualifi ed electrician staff only, who has learnt
these instruction and functions of the device. This device contains protection against
overvoltage peaks and disturbancies in supply. For correct function of the protection of
this device there must be suitable protections of higher degree (A, B, C) installed in front
of them. According to standards elimination of disturbancies must be ensured. Before
installation the main switch must be in position "OFF" and the device should be de-
energized. Don´t install the device to sources of excessive electro-magnetic interference.
By correct installation ensure ideal air circulation so in case of permanent operation and
higher ambient temperature the maximal operating temperature of the device is not
exceeded. For installation and setting use screw-driver cca 2 mm. The device is fully-
electronic - installation should be carried out according to this fact. Non-problematic
function depends also on the way of transportation, storing and handling. In case of any
signs of destruction, deformation, non-function or missing part, don´t install and claim
at your seller it is possible to dismount the device after its lifetime, recycle, or store in
protective dump.
2 / 2
hysteresis
t
t
2
and max. 2x 2.5 mm
2
.
sensor resistance
22.6 KΩ
1.1 KΩ
59 Ω

Publicidad