Technical parameters

PRM-91H/8 PRM-91H/11 PRM-92H
Number of functions:
Supply:
pins 2 and 7
Voltage range:
Power input (max.):
Max. dissipated power
(Un + terminals):
8 W
Supply voltage tolerance:
Supply indication:
Time ranges:
Time setting:
Time deviation:
Repeat accuracy:
Temperature coeffi cient:
Output
Number of contacts:
1x changeover / SPDT
(AgNi / Silver Alloy)
Current rating:
Breaking capacity:
4000 VA / AC1, 384 W / DC
Inrush current:
Switching voltage:
Output indication:
Mechanical life:
Electrical life (AC1):
Controlling
Control. voltage:
Power the control input:
Load between 5-10:
Glow tubes connetions:
Control terminals:
Max. capacity of cable control:
- without connected glow-lamps:
Impulse length:
Reset time:
Other information
Operating temperature:
Storage temperature:
Electrical strength:
Operating position:
Mounting / DIN rail:
Protection degree:
Overvoltage category:
Pollution degree:
Dimensions:
Weight:
54 g (1.9 oz.)
Standards:
Recommended socket for DIN rail
Max. current: 10 A
ES-11 (11 pin)
38
ø 3.2
ø 4.2
30
27
10
pins 2 and 10 pins 2 and 10 pins 2 and 10
AC/DC 12 - 240 V (AC 50 - 60 Hz)
AC 0.7 - 3 VA / DC 0.5 - 1.7 W
7 W
4 W
-15 %; +10 %
green LED
0.1 s - 10 days
0.1 s - 100 days
rotaty switch and potentiometer
5 % - mechanical setting
0.2 % - set value stability
0.01 % / °C, at = 20 °C (0.01 % / °F, at = 68 °F)
2x changeover / DPDT
(AgNi / Silver Alloy)
16 A / AC1
8 A / AC1
2000 VA / AC1, 192 W / DC
30 A / < 3 s
10 A / < 3 s
250 V AC / 24 V DC
multifunction red LED
3x10
7
5
0.7x10
in the supply voltage range
AC 0.025 - 0.2 VA / DC 0.1 - 0.7 W (UNI)
Yes
No
2 - 5
0.1 μF
min. 25 ms / max. unlimited
max. 150 ms
-20 .. 55 °C (-4 °F .. 131 °F)
-30 .. 70 °C (-22 °F .. 158 °F)
2.5 kV
any
DIN rail EN 60715
IP40 from front panel
III.
2
50 x 38 x 51 mm (2˝ x 1.5˝ x 2˝)
58 g (2.05 oz.) 58 g (2.05 oz.) 59 g (2.08 oz.)
EN 61812-1, EN 61010-1
ES-8 (8 pin)
38
ø 3.2
ø 4.2
30
Functions
PRM-2H
PRM-91H, PRM-92H
2
Delay ON after energisation
a
U
R
t
2 W
Cycler beginning with pause after
energisation
c
U
R
t
t
t
Delay OFF after de-energisation, instant
make of output
e
S
R
t
Delay OFF after break of control contact
with instant output
g
S
R
t
Impulse relay
i
S
R
PRM-2H
By PRM-2H function is selected by connecting by terminals 2 and 5.
Cycler beginning with impulse
U
2
5
R
t1 t2 t1 t2 t1 t2
Warning
Device is constructed for connection in 1-phase main alternating current and must be
installed according to norms valid in the state of application. Connection according to the
details in this direction. Installation, connection, setting and servicing should be installed by
qualifi ed electrician staff only, who has learnt these instruction and functions of the device.
This device contains protection against overvoltage peaks and disturbancies in supply.
For correct function of the protection of this device there must be suitable protections of
higher degree (A, B, C) installed in front of them. According to standards elimination of
disturbancies must be ensured. Before installation the main switch must be in position "OFF"
and the device should be de-energized. Don´t install the device to sources of excessive
electro-magnetic interference. By correct installation ensure ideal air circulation so in case of
permanent operation and higher ambient temperature the maximal operating temperature
of the device is not exceeded. For installation and setting use screw-driver cca 2 mm. The
device is fully-electronic - installation should be carried out according to this fact. Non-
problematic function depends also on the way of transportation, storing and handling. In
27
case of any signs of destruction, deformation, non-function or missing part, don´t install
and claim at your seller. In case of any signs of destruction, deformation, non-function or
missing part, don´t install and claim at your seller. It is possible to dismount the device after
its lifetime, recycle, or store in protective dump.
2 / 2
Delay OFF after energisation
b
U
t
R
Cycler beginning with impulse after
energisation
d
U
R
t
t
t
Delay OFF responding to make of
control contact regardless its length
f
S
R
t
Delay OFF after make and break of
control contact
h
S
t
R
Pulse generator (puls = 0.5s)
j
U
R
Cycler beginning with pause
U
S
2
5
R
t
t
t
t
t
t
t
t
t
t
t
t
t
t
t
PULS
t
PULS
t2 t1 t2 t1 t2
t1