11.5
Wiring instructions QC03
Intrinsically safe Control Module
Minimum operating values:
- Control supply:
Umin = 6 VDC
Imin = 1 mA
- Power supply:
Umin = 13.5 VDC
Imin = 33 mA
Cable range:
Wire range:
2.5mm
Solid / Stranded wire: 0.2-3.3mm
24-12 AWG
Notes:
1
Installation must be inaccordance
with:
2
Before operation:
3
Barriers:
4
Intrinsically safe equipement
5
Barrier I.S. Entity Parameters must
meet the following conditions:
6
When multiple barriers are used:
DOC.IG.QC01.1 Rev.: B
Terminal connections, with
seperate circuits
1-2 Feedback 2
3-4 Feedback 1
5-6 Control supply
voltage
7-8 Power supply
voltage
Terminal connections,
with common "-"
1-2 Feedback 2
3-4 Feedback 1
5-6 Control
2
max.
7-8 Power supply
2
or
voltage
CSA
Canadian Electrical Code,
Part1
The control module in combination with the pneumatic module must be mounted properly.
Must be FM/CSA Approved and installed in an enclosure
that meets the requirements of ANSI/ ISA S82.01/CEC
part1.
Control equipment connected to the barrier must not use
or generate more than 250Vrms or Vdc.
Must be CSA Approved
Uo =< Ui
Co >= Ci + Cable
* Each I.S. Circuit must use shielded, twisted pairs
* Cable insulation and shielding must extend to within paritioned area of terminals
Certified Document:
No modification permitted without reference to the certifying authority.
Title :
Control Drawing FieldQ
QC03 Smart Modules Intinsically safe
Home page:
www.FieldQ.com
Unclassified or Non
Hazardous Location
IS Approved
Barrier
IS Approved
Barrier
IS Approved
Barrier
IS Approved
Barrier
IS Approved
Barrier
FM
National Electrical Code
(ANSI/NFPA 70) and
ANSI/ISA RP12.06.01
Must be FM Approved
Io =< Ii
Lo >= Li + Cable
Drn.:
Format :
A4
Drw nr.
13
Hazardous or
Classified Location
1
2
3
FieldQ
Control
4
Module
5
QC03
6
-
7
+
8
1
2
3
FieldQ
4
Control
Module
5
QC03
6
-
7
+
8
ATEX
The national wiring practices
of the country of use
Must be certified by an
European Notified body and
installed per manufacturer's
installation instructions
Must be ATEX Approved
Po =< Pi
Scale :
Date :
27/06/2006
Date :
ENOC nr.:
State :
C0542-06
December '06
En
Par. :
Rev. :