DIP Switch Humidity Output Selection
You can change the humidity parameter that is output on the RH channel of HMD65 with the
DIP switches on the component board. Select the parameter you want the transmitter to
output by sliding the parameter's DIP switch to the right (ON). In the example in
(page
15), the selected output parameter is dew point/frost point temperature (T
other DIP switches in the OFF position (left).
The selected parameter uses the default scaling shown in
Table 2 HMD65 Default Parameter Scaling
Parameter
RH
T
d
T
df
A
X
T
w
H
If you need to change the default scaling of a parameter, configure the output
with Vaisala Insight PC software. See the instructions in HMD65 User Guide.
CAUTION!
that the DIP switch selections override the Insight configuration. When using
Insight to configure the output, set all humidity parameter DIP switches to the
OFF position (left) to ensure they do not cause a conflict with the Insight
settings.
Default Scaling for 0 ... 10 V Output Range
0 ... 100 %RH
-40 ... +80 °C (-40 ... +176 °F)
-40 ... +80 °C (-40 ... +176 °F)
3
0 ... 300 g/m
(0 ... 131.1 gr/ft
0 ... 600 g/kg (0 ... 4200 gr/lb)
-40 ... +80 °C (-40 ... +176 °F)
-40 ... 1600 kJ/kg (-9.5 ... 695.6 Btu/lb)
If you use the Insight software to further configure the output, note
Figure 10 HMD65 DIP Switch Example: T
Output Selected
RH
Relative humidity
Td
Dew point temperature
Tdf
Dew point/frost point temperature
A
Absolute humidity
X
Mixing ratio
Tw
Wet-bulb temperature
H
Enthalpy
Table 2 (page
15).
3
)
df
Figure 10
). Keep the
df
15