Install the indoor unit
1. Installation position
If the humidity and temperature on ceiling separately exceed 30℃ and RH80%, please affix the thermal
insulation materials on machine. Please use the glass wool or foaming polyethylene with the thickness of
more than 10mm. (If more than 10mm, please collect them at the position of inlet of ceiling.)
1) This indoor unit can be mounted on the ceiling of 2.5-3.5m high; but, when the ceiling height is higher
than 2.7m, the tape must be sued for site setting.
2) Install and use the hoisting bolt; check whether the installation position can support the unit weight. If
not security, please fasten before installation of unit. The hole distance is marked on installation paper
model; refer to the mounting paper model and find the points to be reinforced.
3) There must have no barrier in 1000mm from the air outlet.
Space required for installation
Exhaust pipe Air inlet
Note: The actual dimensions refer to the actual product.

4.Installation of unit

Exhaust pipe
Model
18K
24K
36K 48K 55K
11
Above 1500
Machine body height (H)
267
230
285
Unit: (mm)
Above 1500
Above 1500