The "DA.BA" microcontroller control unit can be used with 24Vdc motors having a power no higher than 100W.
Characteristics:
This control unit is designed to operate a 24Vdc, 100W motor for actuating road barriers.
• Controls can be given separate pushbuttons (i.e. APRE-OPEN, CHIUDE-CLOSE, P.P.-STEP BY STEP, STOP).
• Designed to receive photocells so that when the infrared beam is interrupted during the close cycle the barrier
changes direction.
• Designed to receive a safety edge (mechanical or electronic) in close cycle.
• Output for a beacon and a Barrier Open Light signal.
• Output to operate a 24V electrolock.
• Automatic close function with adjustable delay.
• Limit stop slowdown with programmable speed adjustment.
• Amperometric obstacle detector with adjustable sensitivity.
• Operation with buffer batteries during mains power cuts (using the special battery charger).
• 7 barriers can be connected in series as slaves using just one master barrier.
• Safety edge fault detector transfers operation to manned mode.
Power Supply:
• 230Vac, ±10%
• 22÷27Vdc, 12A, supplied by 2 sealed lead batteries, 12Vdc - 6.5Ah each connected in series.
Safeties:
• Overload fuse on main power supply
• Overload fuse on auxiliary lines
• Overload fuse on high voltage line
• Converter against peak voltages on high and low voltage
• Electronic overload limiter on motor
ATTENTION: The protection against inverting the battery poles is only effective if the correct fuses are used.
Surge currents are nevertheless generated, being hazardous for both circuit and operator. Special care must
be taken in ensuring the correct poles are respected.
If the control unit is not fitted with a battery charger board it will not operate with buffer batteries.
Installation instructions.
a) Wire according to wiring diagram in the figure, paying special care in ensuring the correct poles are respected.
b) Inhibit all normally closed inputs that are not required: Stop (25), Fc (26), Fa (27), Ftc (28), Asc (29) using the 6 dip-
switches next to the removable terminal block. Their related functions are:
DSW1
Stop push button test
DSW2
Close limit stop test
DSW3
Open limit stop test
DSW4
Photocell test
DSW5
Safety edge test (With safety edge: Dip5= Off; without safety edge: Dip5= On)
DSW6
Select edge type (set Dip5 to Off and one type of edge MUST be connected to the ASC input)
Off= Mechanical safety edge
On= Electronic safety edge
N.B.: If no kind of edge is installed set dip 5 to ON.
If a mechanical edge is connected set dip 5 to OFF and dip 6 to OFF.
If an electronic edge is connected set dip 5 to OFF and dip 6 to ON.
ATTENTION: DO NOT FIT EXTERNAL JUMPERS ON UNUSED INPUTS.
N.B.: If the edge remains armed for at least 10 seconds (therefore also in the event of malfunction), the control unit will
enter the "HOD TO RUN" operating mode, i.e. to action the barrier hold down the APRE (OPEN) pushbutton to
open the barrier and the CHIUDE (CLOSE) pushbutton to close the barrier. When the pushbuttons are released
the barrier will stop. The PROG LED will light up without blinking. After the edge is disactivated, the control unit
returns to normal operation after about 3 sec.
c) Connect the control inputs: PP "Step by Step" (24), Apre "Open" (23), Chiude "Close" (22).
d) Connect the 24Vdc supply (11,12) to any accessories connected to the control unit (e.g. photocells, receivers, etc)
respecting the correct poles. Connect the beacon and any "Barrier Open Light" SBA (24V lamp, max 3W).
e) After having checked the connections, power the control unit at the 230Vac input terminals (1,2).
When powered, the Input LED's should light up: STOP, FT and at least one of the FC or FA LED's.
The PROG LED should blink.
DA.BA Control unit
11