Interruptor de posición para atmósferas con polvo combustible

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 7
Actuation speed V
min
Snap-action contact
Slow-action contact
Minimum force required in actuation direction:
3SE51..-..E, F, R, V1
3SE51..-..C, D
Minimum torque in actuation direction:
3SE51..-..H, T
Drive (Figure 1.1.2)
Minimum torque in actuation direction:
3SE51..-..... / 3SE52..-.....
Switching angle:
3SE51..-..U1. / 3SE52..-..U1.
3SE51..-..U2. / 3SE52..-..U2.
Contact Blocks
Connection designation according to EN 50013
The switching point of snap-action contacts remains constant throughout the
whole service life independent of contact erosion.
Contact
Figure Name
version
1NO/1NC 2.1.1 Standard, snap-action
1NO/1NC 2.1.4 Standard, slow-action
1NO/2NC 2.1.5 Standard, snap-action
1NO/2NC 2.1.6 Standard, slow-action
Technical Data
Degree of protection according to DIN VDE 0470 and IEC 60529:
3SE5112-.....-1DA0
3SE5122-.....-1DA0
For actuator heads R, H80 to H83, K80 to K83
Permissible ambient temperature during operation –25 ... +85 °C
Storage temperature
Maximum surface temperature
Degree of pollution according to DIN VDE 0110
Mechanical service life
Exception for 3SE5...-.CR..
Exception for 3SE51..-..T..
Electrical service life
(with contactor 3RH11, 3RT1016 to 3RT1026)
Utilization category I
/AC-15
e
3-pole contact block
2-pole contact block
Switching frequency
(with contactor 3RH11, 3RT1016 to 3RT1026)
Shock resistance (IEC 60068-2-27)
Repeat accuracy
(Repeated switching, measured at the plunger of the contact block)
Rated insulation voltage U
i
Rated impulse voltage U
imp
Rated operational voltage U
e
at U
> 300 V same potential only
e
Thermal rated current I
th
4
0.1 mm/s
10 mm/s
9 N
18 N
0.25 Nm
0.40 Nm
15°
MLFB
Circuit diagram
3SE5000
–.C...
–.B...
–.R...
–.L...
–.K...
–.Q...
IP66 / IP67
IP66 / IP67
IP65 / IP67
–40 ... +90 °C
105° C
Class 3
6
15 x 10
operating cycles
6
10 x 10
operating cycles
6
5 x 10
operating cycles
6
10 x 10
operating cycles
100,000 operating cycles
240 V 1.5 A
240 V 3 A
6000 operating cycles / hour
30 g / 11 ms
0.05 mm
400 V
6 kV
400 V
6 A
Short-circuit protection (without welding)
DIAZED fuse links
Utilization category gG
Miniature circuit breaker
Characteristic C
Current carrying capacity AC15 / DC13
Rated current I
at U
:
e
e
3-pole
24 V
AC15
6 A
B300
2-pole
24 V
AC15
6 A
A300
2 / 3-pole
24 V
DC13
3 A
Q300
Maintenance
Exchanging the actuator head
The part-turn actuator is pre-stressed and must be held in position!
Unscrew enclosure cover (1), turn locking plate (2) to the right, pull off actuator
head (3).
Insert new actuator head (3) as far as it goes, turn locking plate (2) to the left,
screw on enclosure cover (1).
Part-turn actuator 3SE5000-0AH00 (left or right-hand switching)
Setting the actuator head for either left or right-hand switching (at the fac-
tory)
Actuator plunger (4) turned to the left by 90° = left-hand switching.
Actuator plunger (4) turned to the right by 90° = right-hand switching.
4
3
2
1
6 A
1 A
120 V
240 V
3 A
1.5 A
120 V
240 V
6 A
3 A
125 V
250 V
0.55 A
0.27 A
3ZX1012-0SE50-0AA0
3
4