NOTE: If you need to install ducts, note that the total duct
length of 3
1 4
should not exceed 140 equivalent feet.
Read the following carefully.
NOTE: It is important that venting be installed using
the most direct route and with as few elbows as possible.
This ensures clear venting of exhaust and helps prevent
blockages. Also, make sure dampers swing freely and
nothing is blocking the ducts.
Exhaust connection:
The hood exhaust has been designed to mate with
a standard 3
1 4
If a round duct is required, a rectangular-to-round
transition adaptor must be used. Do not use less than
a 6 diameter duct.
DUCT PIECES
Rectangular-to-Round
Transition Adaptor*
Wall Cap
90° Elbow
45° Elbow
90° Elbow
45° Elbow
Roof Cap
3
1 4
* IMPORTANT: If a rectangular-to-round transition
adaptor is used, the bottom corners of the
damper will have to be cut to fit, using the tin snips,
in order to allow free movement of the damper.
4
Installation Instructions
EQUIVALENT
LENGTH
5 Ft.
40 Ft.
10 Ft.
5 Ft.
25 Ft.
5 Ft.
24 Ft.
Maximum duct length:
For satisfactory air movement, the total duct length of
3
1 4
not exceed 140 equivalent feet.
Elbows, transitions, wall and roof caps, etc.,
present additional resistance to airflow and are equivalent
to a section of straight duct which is longer than their
actual physical size. When calculating the total duct
length, add the equivalent lengths of all transitions and
adaptors plus the length of all straight duct sections. The
chart below shows you how to calculate total equivalent
ductwork length using the approximate feet of equivalent
length of some typical ducts.
NUMBER
x
USED
x
( )
x
( )
x
( )
x
( )
x
( )
x
( )
x
( )
Total Ductwork
Equivalent lengths of duct pieces are based on actual tests
and reflect requirements for good venting performance with
any vent hood.
should
=
LENGTH
=
Ft.
=
Ft.
=
Ft.
=
Ft.
=
Ft.
=
Ft.
=
Ft.
=
Ft.
31-7000110 Rev. 1