Descargar Imprimir esta página

Siemens SIRIUS 3RW4900-0NC00 Instructivo página 5

Módulo de comunicación profinet para arrancador suave 3rw44

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 11
PROFINET Communication Module for Soft Starter 3RW44
DANGER
!
Hazardous voltage.
Will cause death or serious injury.
Turn off and lock out all power supplying this
device before working on this device.
www.siemens.com/sirius/manuals
Further information:
PROFINET Communication Module manual
Order No. 3ZX1012-0RW40-0AB0
1. Inserting the PROFINET communication module
NOTICE
Danger of material damage.
Before inserting the PROFINET communication module
de-energize the 3RW44 soft starter.
Proceed as follows:
1. Remove the cover as shown in Fig. 1 on page 23.
2. Insert the PROFINET communication module into the device as shown in Fig. 2 on page 23.
3. Fasten the PROFINET communication module with the attached screws.
4. Insert the PROFINET connecting cable into one of the sockets of the communication module.
NOTE
A maximum of two straight connectors, or one straight plus one angled connector, can be used at the same time.
5. Switch on the supply voltage.
The LED BUS flashes yellow. The communication module has been inserted correctly, but has not yet been activated.
3ZX1012-0RW40-0NA1
NOTICE
The shield of the PROFINET cable must be brought to the
grounding potential of the equipment.
3RW44 Soft Starter manual
Order No. 3ZX1012-0RW44-1AC1
NOTE
The PROFINET communication module can only be operated on
3RW44 devices with product version "E12" or higher.
English
5

Publicidad

loading