6. Commissioning, operation

6.7 Switching functions

Hysteresis function
If the system pressure fluctuates around the set point, the hysteresis keeps the
switching status of the outputs stable. With increasing system pressure, the
output switches when reaching the switch point (SP).
Contact normally open (HNO): active
Contact normally closed (HNC): inactive
With system pressure falling again, the output will not switch back before the reset
point (RP) is reached.
Contact normally open (HNO): inactive
Contact normally closed (HNC): active

Window function

The window function allows for the control of a defined range.
When the system pressure is between window High (FH) and window Low (FL),
the output switches on.
Contact normally open (FNO): active
Contact normally closed (FNC): inactive
When the system pressure is outside window High (FH) and window Low (FL),
the output does not switch on.
Contact normally open (FNO): inactive
Contact normally closed (FNC): active
Pressure sensor SPAW
Fig.: Hysteresis function
Fig.: Window function