Siemens sitrans LR260 (HART) Manual De Inicio Rápido página 17

Ocultar thumbs Ver también para sitrans LR260 (HART):
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 75
1.3. Sensor Units
Selects the units for the Quick Start variables (high and
low calibration point, and level, distance, or space).
1.4. Operation
sensor reference point
NO
SERVICE
LEVEL
Operation
SPACE
types
DISTANCE
Default: Distance
1.5. Low Calibration Point
Distance from Sensor Reference to Low Calibration Point: usually process empty level. See
Operation (1.4.) for an illustration.
Range: 0.0000 to 30.000 m
Values
1.6. High Calibration Point
Distance from Sensor Reference to High Calibration Point: usually process full level. See
Operation (1.4.) for an illustration.
Range: 0.0000 to 30.000 m
Values
1.7. Apply? (Apply changes)
In order to save the Quick Start settings it is necessary to select Yes to apply changes.
Options
Press Mode
to return to Measurement mode. SITRANS LR260 is now ready to operate.
7ML19985XH81
low cal.point
The SITRANS LR260 stops updating measurements and associ-
ated loop current. Last valid measurement is displayed.
Distance to material surface referenced from Low Calibration
Point (process empty level).
Distance to material surface referenced from High Calibration
Point (process full level).
Distance to material surface referenced from Sensor Reference
Point.
YES, NO, DONE (Display shows DONE when Quick Start is successfully
completed)
SITRANS LR260 (HART) – QUICK START MANUAL
Options
high cal.
point
distance
space
level
M, CM, MM, FT, IN
Default: M
Page EN-15

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Sitrans lr260

Tabla de contenido