Check:
„ the condition of the instrument (not damaged, incomplete, or incorrectly closed),
„ the condition of the insulation on the leads, connector, and housing.
„ the connections: the terminals, the cable, the connectors, the socket,
„ the markings on the tester and the connecting cable (300V CAT II).

2.2. FUNCTIONAL TEST

The functional test consists in verifying that the protective conductor (PE) is correctly earthed and that
its voltage with respect to earth is zero.
„ Connect the cord with the type 2 connector to the CA 6651. Screw on the locking ring.
„ Connect the type 2 connector to the charging terminal of the electric vehicle.
Indicator.
„ Place your bare finger on the side of the housing, at the specialized location.
Once the instrument is connected, do not touch the connector until the PE has been tested: the
accessible metallic part of the connector may be at a hazardous voltage.
If the voltage of the PE with respect to earth is not zero, the indicator lights.
Determine the cause of this fault, probably a wiring error, and eliminate it.