N O Zzle Clean I N G An D Replacem En T - Ecoflam Multicalor 45 Manual De Instrucciones

Quemadores mixtos gas/ gasoleo
Ocultar thumbs Ver también para Multicalor 45:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 29
420010239601 M ul t i c al or 45 ÷ 140 PR/ PR
EN
Use only the suitable box wrench provided for this operation to remove the nozzle, taking care to not damage the elec-
trodes. Fit the new nozzle with the same care. N ot e: Always check the position of electrodes after having replaced the
nozzle (see illustration). A wrong position could cause ignition troubles.
The control of the detector current shall be carried out by plugging a microampe-
rometer with full scale at 1000 µA (D.C.) in series with the UV-cell. If the detec-
tor current is too low verify the connection between phase and neutral of the bur-
ner and the grounding of the burner itself. Minimum required detector current is
200 µA.
F
HLBT
R
HLoil
V
B
HLgas
R

N O ZZLE CLEAN I N G AN D REPLACEM EN T

FLAM E D ETECTO R SYSTEM CH ECK
REM O VI N G TH E BLAST TU BE
D ESCRI PTI O N O F CO N TRO L PAN EL
D
SAL
0
1
RWF 40
0: OFF
1: ON
G
C
0=STOP
SAMA
1=UP
2=LOW
3=AUTO
E
0=STOP
SAgG
1=OIL
2=GAS
3=AUTO
A
SA s.r
6 mm
SW = BLACK
BL = BLU
A - reset key
B -
operating lamps (orange=light-oil; green= gas)
C - selector:
OUT =
loking of devoices for operating at intermediate outputs
UP
=
operation at max. output
LOW =
operation at min. output
=
automatic operation
AUTO
D -
ON/OFF switch
E - selector:
0 = STOP
1 =
light-oil operation
2 =
gas operation
3 = automatic operation
F -
termal lock-out lamp
G -
modulating unit RWF 40 (optional)
18
3,5 mm
SW
1
LGB 22
2
BL
BL
QRA
SW

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Multicalor 70Multicalor 100Multicalor 140

Tabla de contenido