Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 85

Operating area

For proper functioning and a good temperature
distribution, the stove shoul be positioned in a
location where it is able to take in the air necessary
for combustion of the pellet (about 40 m
available), as laid down in the standard governing
the installation and in accordance with local national
standards.
The volume of the room must not be less than 30 m
The air must come in through permanent openings
made in walls (in proximity to the stove) which give
onto the outside, with a minimum cross-section area
of 100 cm
.
2
These openings must be made in such a way that it
is not possible for then to be obstructed in any way.
Alternatively, the air can be taken from rooms adjacent
to the one which needs ventilating, as long as they are
provided with an air intake from the outside, and are
not used as bedrooms or bathrooms, and provided
there is no fi re risk such as there is for example in
garages, woodsheds, and storerooms, with particular
reference to what is laid down in current standards.
It is not permissible to install the
stove in bedrooms, bathrooms, or
in a room where another heating
appliance is installed (fi replace, stove etc.)
which does not have its own independent
air intake.
Locating the stove in a room with an
explosive atmosphere is prohibited.
The fl oor of the room where the stove is to
be installed must be strong enough to take
its weight. If walls are fl ammable, maintain
a minimum distance of 10 cm at the rear
(A), of 10 cm at the side (B) and 100 cm at
the front.
If the room contains objects which are
believed to be particularly delicate, such
as drapes, sofas and other furniture,
their distance from the stove should be
considerably increased.
Connection to the external air intake
It is essential that at least as much air must be able
to fl ow into the room where the stove is installed as
is required for proper combustion in the appliance
and for the ventilation of the room.
This can be effected by means of permanent
openings in the walls of the room to be ventilated,
which give onto the outside, or by single or
collective ventilation ducts.
For this purpose, on the external wall near the
stove, a hole must be made with a minimum free
cross-section of 100 cm
hole of 12 cm diameter or a square hole 10x10 cm)
In the presence of wood fl oors,
install a fl oor protection surface in
compliance with the rules in force in
the country
4
3
/h must be
. (equivalent to a round
2
.
3
protected by a grille on the inside and the outside.
The air intake must also: communicate directly
with the room where the thermostove is installed
be protected by a grille, metal mesh or suitable
guard, as long as this does not reduce the area
below the minimum. Be positioned in such a way
as to be impossible to obstruct.
It is not compulsory to connect the
air intake directly with the stove
(so that it draws air directly from
outside), but it is essential at all
events to ensure an airfl ow of 50 cubic
metres per hour by the use of a hole of the
dimensions given. See standard UNI 10683.
10 cm (A)
10 cm (A)
Min.
Min.
100
cm
2

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Slim 8cSlim 10cSlim 60Slim 75Slim 90001126

Tabla de contenido